3
INSTALLATION
Model
Dimensions (mm)
Weight
(kg)
A
B
C
D
RUA-NP4ATS
615
405
685
730
230
RUA-NP5ATS
615
405
685
730
230
RUA-NP6ATS
810
550
690
1000
310
RUA-NP8ATS
810
550
690
1000
330
RUA-NP9ATS
850
575
880
1200
410
RUA-NP10ATS
800
625
780
1300
420
Fig. 4. Center of Gravity
2. INSTALLATION
2.1 Ducting Arrangement
Tools and Instruments
–
General tools for
ducting.
Connection
–
Pre-drilled duct flanges are
provided at the supply and return air duct
connections. A field-supplied or optional filter box
with filter must be installed at a proper location in
the return air duct. It is recommended that flexible
duct connections be installed to minimize sound
and vibration transmission. All ducts running
outside must be sufficiently insulated and
weatherproofed.
2.2 Condensate Drain Piping
Tools and Instruments
–
General piping tools.
Drain Trap
–
A female piping thread screw
connection is provided at side of the unit.
Dimension "L" in Fig. 5 should be sufficiently
longer than the negative fan pressure at the drain
connection (50mm to 100mm, depending on the
return air duct design). Always fill the trap with
water.
Fig. 5. Condensate Drain Connection