Electrical Wiring
-19 -
Electrical Wiring
5. Electrical Wiring
Tools and Instruments
One Set of Wiring Tools, Electrical Testers (Clamp Meter)
5.1 Schedule Check
Confirm that the field-selected electrical components (main power switch, fuses, wires, conduit connections, wire
terminals) are properly selected according to the table and to ensure that they comply with national and local codes.
It is recommended that the main power switch be locked at the OFF position to prevent against accidental supply
of the power during unit servicing.
Electrical Data Table
Model
Unit Main Power
Starting Current
Running Current
Indoor Unit
RPS-140AN
1 PHASE , 230V/60Hz
RAM-140FPS 3 PHASE , 230V/60Hz
8A 14A
5.2 Main Power Wiring Procedures
(1) Confirm the electrical power is not supplied in the installation location prior to any electrical installation work.
(2) Access to the magnetic switch box is provided with the service cover, which is fixed with screws.
(3) Install the field-supplied main switch box at the properly selected location.
(4) Install conduit connectors in the hole for power wiring.
(5) Connect the main power wires and the grounding wires through the connector screw of terminals in the
magnetic switch box.
(6) Firmly connect the wires with wire terminals to the unit screw terminals according to wiring label attached in the
magnetic switch box.
(7) Reversal Phase Protection for the Three phase model RPS-140AN.
Because the rotation direction of the orbiting scroll of the scroll type compressor is fixed, the scroll compressor
is equipped with a Reversal Phase Protection Relay. If each phase R, S or T of the power source is incorrectly
connected, the compressor will not start due to activation of the reversal phase protection relay. Therefore in
order to check the correct wiring connection, the utilization of a phase sequence indicator is recommended
when the unit is started after installation of the unit.
‧
If the phase is wrong, exchange two of the three wires connected from the main power source to the main
terminals of the unit as indicated with the dotted lines, and then check the rotation direction of the phase
sequence indicator once again. Do not exchange the wires in the unit side in order to protect the compressor
against the reversal rotation.
Outdoor Unit
R
S T
Unit Side
Power Source
RAM-140FPSB 1 PHASE , 230V/60Hz
Outdoor Unit