5
ELECTRICAL WIRING
7
DSW3: Capacity Code Setting
No setting is required, due to setting before shipment. This
dip switch is utilized for setting the capacity code which
corresponds to the Horse Power of the indoor unit.
HP
1.0
1.5
Setting position
ON
1 2 3 4
ON
1 2 3 4
DSW5: Refrigerant Cycle No. Setting
Setting is required. Setting position before shipment are all
OFF (Refrigerant cycle No. O)
Before shipment
ON
1 2 3 4
Cycle No.
0
1
2
3
Setting Position
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
Cycle No.
4
5
6
7
Setting Position
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
Cycle No.
8
9
10
11
Setting Position
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
Cycle No.
12
13
14
15
Setting Position
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
DSW7: Fuse Recover
Not setting is required. Setting position before
shipment is all OFF.
ON
OFF
In case of applying high voltage to the terminal
1,2 of TB1, the fuse on the PCB1(M) is cut.
In such a case, firstly correct the wiring to TB1
and then turn on (as showing beside).
ON
OFF
CAUTION:
Do not turn the air louver by hand. If moved, the
louver mechanism will be damaged! (in all units)
Adjust the vertical deflectors by hand to discharge air in the
required direction.
Do not swing 1 blade at left side and 2 blade at right side of the
vertical deflection.
Automatic Setting of louver:
When the unit operation is stopped, two air louvers are stopped
at closing position automatically
.
Horizontal
Deflector
Vertical
Deflector