15.2 PiPinG connection
15.2.1
Position of pipe connection
The piping connection is performed inside the indoor unit. The
pipe connection can be performed from 3 directions, rear, right
and upper. For rear and upper pipe connections, the plastic cap
is attached at knockout hole for the refrigerant pipe and the drain
pipe. Cut out the knockout hole of cap for piping and attach the
cap again after running the refrigerant pipe through the cap.
Hole position and size
right end of
indoor unit
ceiling
View from front
View from bottom
Front
right end of
indoor unit
Wall
?
n o t e
When the optional drain-up mechanism is attached, refer to the installation
manual of itself.
Position of pipe connection
Cap (rear side)
Gas pipe
Suspension band
Liquid pipe
Drain pipe
If the liquid pipe contacts strongly to the plate, noise caused by
refrigerant flowing may increase. Suspend the local liquid pipe by
suspension band to prevent dangling.
right side
upper side
rear side
Cap (rear side)
146 (liquid pipe)
94 (gas pipe)
147 (drain pipe)
Drain pipe connection
(VP20, right side)
190 (liquid pipe)
Drain pipe connection
(VP20, left side)
205 (gas pipe)
138 (drain pipe)
117 (liquid pipe)
107 (gas pipe)
40 (drain pipe)
View from right
View from front
Piping from rear side
Upper surface
Cap (rear side)
Drain pipe connection
(VP20, left side)
View from front
Piping from right side
Hole for drain pipe connection
(knockout hole)
View from right
Piping from upper side
View from bottom
Cap (upper side)
rear side of
indoor unit
rEFrIGErANT PIPING WOrK
PMML0254A rev.4 - 12/2018
29