![Hitachi RCI-3.0UFE1NH Скачать руководство пользователя страница 26](http://html.mh-extra.com/html/hitachi/rci-3-0ufe1nh/rci-3-0ufe1nh_installation-and-maintenance-manual_2139381026.webp)
1
Prepare a polyvinyl chloride pipe with a 32mm outer diameter.
2
Fasten the tubing to drain hose with the adhesive agent and factory-supplied clamp. The drain piping must be
performed with a
down-slope pitch of 1/25 to 1/100.
Hose band (Accessory)
1/25 to 1/100
Down-Slope
Unit
Drain Hose (Accessory)
Hose Band
(Accessory)
Vinyl Chloride
(Field Supplied)
Drain Hose
(Accessory)
Drain Pipe Connection
Upward Slope
Rising part
Common Drain Piping
Drain Pipe
Connection
1/25 to 1/100 Down-Slope
This drain pipe shall
be separated from
other pipes
100mm Min.
850mm Max.
* Total length of a+b+c(mm) : a≤300, b≤850, c≤50, a+b+c≤1100
* In case of lifting the drain pipe at outlet part, perform the drain piping work as shown in the above figure.
3
Insulate the drain pipe after connecting the drain hose.
Hose Band (Accessory)
Packing (5Tx270x270)
(Accessory)
(Unit: mm)
INSTALLATION AND MAINTENANCE
HO2019289HA
20