![Hitachi RCI-3.0UFE1NH Скачать руководство пользователя страница 19](http://html.mh-extra.com/html/hitachi/rci-3-0ufe1nh/rci-3-0ufe1nh_installation-and-maintenance-manual_2139381019.webp)
2 Tools and Instruments for Installation
Number
Tool
Number
Tool
1
Standard screwdriver
8
Knife or wire stripper
2
Vacuum pump
9
Leveler
3
Charge hose
10
Hammer
4
Pipe bender
11
Churn drill
5
Adjustable wrench
12
Pipe expander
6
Pipe cutter
13
Inner hexagon spanner
7
Cross head screwdriver
14
Measuring tape
3 Installation of the Indoor Unit
!
DANGER
Do not install the indoor unit in a flammable environment to avoid fire or an explosion.
!
WARNING
• Check to ensure that the ceiling slab is strong enough. Otherwise the indoor unit may topple, and fall down causing injury.
•
Do not install the indoor unit outdoors. If done, an electric hazard or electric leakage will occur.
3.1 Initial Check
•
Install the indoor unit with a proper clearance around it for operation and maintenance space, as shown in Fig.3.1.
•
Provide a service access door near the unit piping connection area on the ceiling.
• Ensure that the ceiling has a sufficient strength to hang the indoor unit.
• Check that the ceiling surface is flat for the air panel installation work.
Piping connection
Service access door
Service access door
Service access door
Piping connection
Piping connection
Distance from Wall Side
500mm Min.
100mm Min.
500mm Min.
1000mm Min.
100mm Min.
Piping
connection side
Service space
Fig. 3.1 Space around Indoor Unit
INSTALLATION AND MAINTENANCE
HO2019289HA
13
EN