d) In case that upper side obstacles exist (serial units)
e) In case of front side and either of the sides are open (serial units)
200
300
0 < L ≤ 1/2 H A ≥ 500
1/2 H < L ≤ H A ≥ 1000
≤ 300
f) In case that surrounding wall exist (serial units)
0 < L ≤ 1/2 A ≥ 500
1/2 H < L ≤ H A ≥ 1000
A
L
1000
0 < L ≤ 1/2 H A ≥ 200
1/2 H < L ≤ H A ≥ 350
g) Horizontal (multiple units)
h) Vertical (multiple units)
0 < L ≤ 1/2 H A ≥ 100
1/2 H < L ≤ H A ≥ 200
≥ 1000
≥ 400
≥ 2000
≥ 250
400
250
250
400
250
≥ 250
Do not stack more than two units in height. - Close gap (*) to avoid recirculating discharge air flow.
UNIT INSTALLATION
PMML0506 rev.2 - 01/2021
7