Table 10-3 LED lighting mode at the thermistors troubled
When the connectors of the thermistors are disconnected or the thermistors is open or short, LD301 (red) lights and
LD302 (red) blinks so that they indicate troubled parts. Combinations of LD301 and LD302 are set up for indicating troubled
thermistors. The correspondences between the number of blink time and troubled parts are shown as Table 10-3. Look in the
table (LD301 and LD302 blink) for troubled parts, and if the disconnections of them are checked out, they are replaced.
If you can see two or more troubled thermistors, a small number of blink takes precedence of others.
The electric expansions valve thermistor is put togrther with 3 pieces, when replacing the thermistor, replace one set of 3 pieces
as taking care of positioning. If you don't do so, the unit may not operate normally and its cooling and heating performance
may drop.
Be ware that only an open-circuit for OH thermistor has to be checked in 5 minutes after the compressor starts.
If the unit operates abnormally after replacing the thermistor, replace the control P.W.B. because it malfunctions.
The OH thermistors are detecting the compressor head temperatures. If the temperature rises over 118˚C, the compressor
in the cycle will be stopped to protect itself and LD301 will blink 6 times (OH STOP). When the compressor temperature
fells under 105˚C, the compressor will restart. During OH STOP, the fan continues to spin. The other cycles without a
trouble operates normally.
If OH STOP often occurs, the refrigerant may be leaking.
LED lighting mode
RAM-55QH5
RAM-65QH5
Lights
Lights
Lights
Lights
Lights
Lights
Lights
Lights
Lights
OH thermistor
DEF thermistor
Outdoor temperature thermistor
Electric expansion value thermistor (thin pipe 1)
Electric expansion value thermistor (thick pipe 1)
Electric expansion value thermistor (thin pipe 2)
Electric expansion value thermistor (thick pipe 2)
Electric expansion value thermistor (thin pipe 3)
Electric expansion value thermistor (thick pipe 3)
1 blink
2 blinks
3 blinks
4 blinks
5 blinks
6 blinks
7 blinks
8 blinks
9 blinks
LD301
LD302
0.04V or less
Open
4.96V or more
0.04V or less 4.94V or more
0.04V or less 4.94V or more
Short
Troubled thermistor
Judgement
Содержание RAM-55QH5
Страница 31: ... 30 CAPACITY DIAGRAM RELATED TO THE PIPING LENGTH MODEL RAM 65QH5 ...
Страница 37: ...CIRCUIT DIAGRAM MODEL RAM 55QH5 39 L C023 C022 C002 C001 C025 C024 N ...
Страница 38: ...CIRCUIT DIAGRAM MODEL RAM 65QH5 41 L C023 C022 C002 C001 C025 C024 N ...
Страница 41: ... 45 ...
Страница 46: ... 51 Outdoortemperature STAROTP_C TSKTM1_C1 Outdoortemperature STAROTP_C TSKTM1_C2 ...
Страница 47: ... 53 ...
Страница 48: ... 55 ...
Страница 49: ... 57 ...
Страница 50: ... 59 ...
Страница 68: ... 77 5A ...
Страница 75: ... 84 ...
Страница 76: ... 85 5 Reversing valve control circuit Fig 5 1 ...
Страница 79: ... 88 8 Overload control circuit OVL control circuit Fig 8 1 Overload Control System Configuration Fig 8 2 ...
Страница 91: ... 103 ...
Страница 92: ... 104 ...
Страница 98: ... 110 TROUBLESHOOTING OF THE SYSTEM POWER MODULE ...
Страница 99: ... 111 ...
Страница 100: ... 112 ...
Страница 102: ... 114 three three inlet 3 Cut off the three pipes at the side and bottom of Reversing valve ...
Страница 103: ... 115 ELECTRIC EXPANSION VALVE PIPE THERMISTOR POSITION CHARTS MODEL RAM 55QH5 MODEL RAM 65QH5 ...
Страница 108: ...HITACHI PM NO 0312E Printed in Malaysia RAM 55QH5 RAM 65QH5 ...