Hitachi RAM-200FPS Скачать руководство пользователя страница 15

15 

Model

 

The factory 

refrigerant 

charging 

weight 

  (kg)

 

Additional 

refrigerant 
upper limit 

(kg) 

RAM-200FPS(D) 

5.0 

13.5 

RAM-250FPS(D) 

5.5 

RAM-270FPS(D) 

6.5 

 

2

 

After locking work is completed, please implement air leakage test.

 

Note

1. The work that after use the flare nut to connect pipe and stop valve, will be effective.

 

2. Because check joints and flare nut can not connect, so please use the charging hoses. The spindle valve cap of stop 

valve is removed, due to internal O-ring and thread will be opened, the voices caused by gas emitting, which has 
nothing to do with the leakage.

 

3. Do not apply an abnormal big force to the spindle valve at the complete opening (5.0 N-m or smaller). 

5) Insulate the unions and flare-nuts at the piping connections completely. Insulate the liquid piping and gas piping completely to avoid 

decreasing of performance and dewing on the surface of the pipe. 

6) In order to prevent rainwater invasion the unit, make sure to install the pipe cover, and installation thermal insulation material where 

the pipe is through the unit, so that it can not have gaps happening. 

  5.3 Vacuum   

1) Details stop valve operation, please refer to the attention of nameplate inside service cover description. 
2) Connect a manifold gauge to the check joints at the both sides. Continue vacuum pumping work until the pressure reaches-0.1MPa 

(-750mmHg) or lower for one to two hours. 

3) After vacuum pumping work, stop the mani-fold valve

’s valve, stop the vacuum pump and leave it for one hour. 

Check to ensure that 

the pressure in the mani-fold gauge does not increase

4) Because check joints and flare nut can not connect, so please use the charging hoses. After the work, please tighten the flare nut with 

16N 

• m of torque. 

5) Check for any gas leakage at the flare nut connections, or brazed parts by gas leakage tester or foaming agent. The following is 

recommended for foam testing fluid [Field-supplied (NUPRO "SNOPP" or

 

Yokogawa & Co., Ltd. 

”キュポフレックス”

)], component is not 

clear which is general household cleaners do not use the liquid as a foam testing.   

6) Vacuum drying determination example

 

 

 

 

 

 

 

 

 

 

 

Note

1. When remove the spindle valve cap of stop valve, there may be slight refrigerant leakage sound is normal. 

2. Use tools and measuring instruments only for the new refrigerant (R410A) which directly touch refrigerant. 
3. If vacuum degree of -0.1MPa (-750mmHg) is not available, it is considered that leakage exists. Check for any gas 

leakage once again. If no leakage exists, operate the vacuum pump for one to two hours. 

 

 

 

 

  5.4 The Additional Refrigerant   

1) Outdoor unit has been filled with refrigerant, but still based on the length of pipe filled with an appropriate amount of refrigerant.

 

The 

filling amount of refrigerant, please following the liquid piping length and the capacity of the indoor unit calculation, the results please fill 
in "                                    ". 

Calculation formula 

 

W

Additional refrigerant of liquid pipe (kg) = W11+W12+W13 

W11

Φ

12.7 liquid pipe length (m)                           

×

0.12(kg)= 

W12

Φ

9.53 liquid pipe length (m)                           

×

0.07(kg)= 

W13

Φ

6.35 liquid pipe length (m)                           

×

0.03(kg)= 

 

W Total=                                (kg) 

2) Fully open the gas line stop valve and slightly open the liquid line stop valve. 
3) Cooling operation, then for charging refrigerant, connect the gauge manifold using 

charging hoses with a refrigerant charging cylinder to the check joint of the liquid line 
stop valve. (Refrigerant charging quantity of tolerance in the ± 0.1kg around.) 

4) Fully open the liquid line stop valve after completing refrigerant charge. 
5) Finally, please lock the spindle valve cap of liquid stop valve in according with the 

following tightening torque. 

 

              The cap tightening torque

 

Liquid 

20 N

Gas 

49 N

 

additional refrigerant (kg) 

Additional refrigerant W 

exceeds the amount of 
additional refrigerant filling 
upper limit, adjust the length 
of piping, such that W does 
not exceed the value of upper 
limit.

   

Please implement vacuum drying determination, to confirm whether water exists within the system. If moisture is present, Please 
extend the vacuum time or installation the drying filter until no moisture is present within the system.

 Be sure to do this work, 

otherwise in the future the unit could easily lead to failure, and difficult to handle.   

V

a

cu

u

D

e

g

re

e

 

Vacuum Time (min) 

Vacuum Time and Vacuum Degree 

Outside air temperature 23

 

Vacuum pump stop 

After the vacuum pump 
stop, the vacuum degree 
rebound phenomenon 

V

a

cu

u

D

e

g

re

e

 

Vacuum Time (min) 

The system includes water vacuum time and 
vacuum degree 

Outside air temperature 20

 

System with water 

System without water 

V

a

cu

u

D

e

g

re

e

 

Vacuum Time (min) 

Figure3

Outside air temperature vacuum time 

and vacuum degree 

System with water, 
outside air 

temperature 20

 

System with water, 
outside air 

temperature 10

 

System without water, outside air 
temperature do not affect 
 

Содержание RAM-200FPS

Страница 1: ...y or death Enforcement matters Machine with a ground terminal the user must follow the instructions for ground work Prohibitions Enforcement matters Indicating the general behavior Non specific object About electrical works DANGER When perform electrical work please have a qualified personnel Please note that the construction is not completely by yourself there will be occurred an electric shock P...

Страница 2: ... system which all indoor units are operated simultaneously the total indoor unit capacity should be less or equal to the outdoor unit capacity For the system which all indoor units are not operated simultaneously the total indoor unit capacity is available up to maximum against the outdoor unit capacity 1 2 Operation temperature range Condition Item Air inlet temperature of outdoor unit Air inlet ...

Страница 3: ... shall be used with the flaring tube adjustment gasket 1mm Using the 1 2H pipe situation can not be processed R410A special flaring tool can be used directly in the R407C Flaring for Tubes Extrusion Adjustment Gauge not use Dimensional Control for Extrusion Portion of Tube after Flaring Pipe Bender Using the 1 2H pipe situation can not be processed Please use the elbow welding connection Bending E...

Страница 4: ...6 15 88 19 4 19 7 19 05 23 3 Can not be processed 1 2H material Please use the attached flare connecting pipe Pipe thickness selected With the design pressure changes the pipe thickness and material should also be changed Pipe Size Existent Type New Refrigerant R22 R407C R410A Thickness Material Thickness Material Thickness Material Φ6 35 0 6 O 0 8 O 0 8 O Φ9 53 0 8 O 0 8 O 0 8 O Φ12 7 0 8 O 0 8 O...

Страница 5: ...is a high level of oil mist salty air or harmful gases such as sulphur 12 Do not install the outdoor unit where the electromagnetic wave is directly radiated to the electrical box 13 Install the outdoor unit as far as at least 3 meters from the electromagnetic wave radiator Strong wind blowing directly against the product installation method Installed on the roof and no buildings surrounding and t...

Страница 6: ...ed 350 Above 300 Above 100 Above Front Side Note Must install the wind break cover plate Option and the both sides must be opened Note Must be opened on both sides A separate installation A row installation two more 350 Above 300 Below 350 Above 300 Below 1000 Above 350Above 1000 Above 100Above 350 Above Setting two sets situation 300 Below 100 Above 100Above 300 Below 1000 Above Front Side 350 Ab...

Страница 7: ...sealed A separate installation A row installation two more Front Side 50Above 100Above 700 Above Note Must install the wind break cover plate Option and the both sides must one side be opened at least With the unit rear side same direction 350 Above 700Above Note Must install the wind break cover plate Option and the both sides must be opened 700Above 350Above 150 Above 700Above 100 Above A separa...

Страница 8: ...t to withstand full weight of the outdoor unit 560 Hole 4 Φ16 x 23 5 Long Hole If ensure 170 dimension and without interference with foundation base it can be downward the piping work To avoid the unit vibration transmitted to the buildings if necessary to install anti vibration rubber Fixed Bracket Fielded supplied 21mm Below A After Cut Off Concrete Anchor Bolt Shelf Width 60 mm Standard Parts O...

Страница 9: ... easy to produce powder Cautions for refrigerant piping work for example 2 Piping Direction The pipe can be connected in four directions Convex Drain Connector Washer Base Drain Hole When installing pipe through the wall Secure a cap at the end of the pipe Hole of wall Attach a cap or vinyl tape Attach a cap or vinyl tape Attach a cap or vinyl tape Do not place the pipe directly on the ground Rubb...

Страница 10: ...lease make the gap of the upper A division remove part of piping In the unit s internal piping and wiring do not interfere with each other 2 3 Connection piping bending use the pipe bender 2 4 In order to metal plate s burrs does not hurt to wiring and piping Please use the insulation material Field supplied materials to protect them Open the service cover essentials 1 Please remove the left screw...

Страница 11: ...m Piping Length Actual Length L1 L2 l 3 100m Below Equivalent Length L1 L2 l 3 120m Below The Total Length L1 L2 l0 l1 l2 l 3 250m Below Maximum Lift between Outdoor Unit and Indoor Unit The outdoor unit is higher than that of indoor unit H 1 40m Below The outdoor unit is lower than that of indoor unit H 1 30m Below Between each indoor unit H 2 15m Below Maximum Piping Length Between Each Multi ki...

Страница 12: ...connected to the indoor unit be sure to use an optional parts of the multi kit pipe set in order to prevent the uneven distribution of the refrigerant and causing the unit s capacity reduction Do not connect using the connector 1 Line branch use the line branch pipe As shown below Main pipe The pipe between each multi kit pipe or the pipe between outdoor units to first multi kit pipe Main Branch T...

Страница 13: ... Correct Setting Wrong Setting First Main Branch Second Main Branch First Branch Second Branch Third Branch First Main Branch Second Main Branch First Branch Second Branch Third Branch X Wrong Outdoor Outdoor Outdoor Outdoor First Main Branch First Main Branch Second Main Branch Second Main Branch First Branch First Branch Second Branch Second Branch Third Branch Third Branch X Wrong Fourth Branch...

Страница 14: ...vibration of the piping Pay special attention in case of short piping length 4 Please perform the air tight test Connect the gauge manifold using charging hoses with a vacuum pump or a nitrogen cylinder to the check joints of the liquid line and the gas line stop valves Perform the air tight test Connect a manifold gauge to the check joints of the liquid and gas stop valves in the outdoor unit Do ...

Страница 15: ...nt R410A which directly touch refrigerant 3 If vacuum degree of 0 1MPa 750mmHg is not available it is considered that leakage exists Check for any gas leakage once again If no leakage exists operate the vacuum pump for one to two hours 5 4 The Additional Refrigerant 1 Outdoor unit has been filled with refrigerant but still based on the length of pipe filled with an appropriate amount of refrigeran...

Страница 16: ... will result in weight percent composition changes so can not directly add refrigerant treatment must be re processing system 5 6 Caution of Measure Pressure Data from The Check Joints Measure pressure data of work please from the check joints of gas line stop valve right figureⒶ and the check joints of piping line right figureⒷ to connect And then please according to the different operation state...

Страница 17: ...Supply 3Φ 60Hz Maximum Current A ELB Earth Leakage Breaker Power Switch Power Supply Size mm2 Earth Wire Size mm2 Transmission Cable Size Number of Poles Rating Sensitivity Current mA Rating Current A Switch Capacity A Fuse Capacity A 1 2 2 3 4 5 RAM 200FPS 230V 22 3 30 30 60 30 3 5 5 5 2 Core Shielded Twist Pair Cable 0 75mm2 Total Length 1000m Below RAM 250FPS 29 40 40 5 5 RAM 270FPS 37 100 50 1...

Страница 18: ...tion wiring construction The transmission cable of indoor and outdoor unit and the 220V power source cord be sure to keep the distance of more than 5 6cm Therefore do not use the coaxial cable If the transmission cable and power source cord connecting wrong will cause the PCB of the outdoor unit burning Please pay special attention 10 Indoor and outdoor unit s power source cord and connection wiri...

Страница 19: ...gs shall be attached the insulation tape or insulation sleeve Χ Ο Fold the wire and reserve for a maintenance operation the desired length Prevent need to remove the wiring plug for maintenance Cord Band Operation 1 When wire through the cord band appropriately tighten it as show below 2 Make sure the cord with high and low pressure sensor isolation 3 Tighten the cord to be isolated with pipe comp...

Страница 20: ...Do not input the power source to the terminal No 1 2 of transmission wiring 3 When power source wiring phase error the unit can not be operated and the remote controller display alarm code 05 At this time please refer to the electrical box caution nameplate check the phase of the first side and replace it The phase of the replacement work please process under the power source turn off 4 Does the o...

Страница 21: ... operation 3 2 Depress RUN STOP switch The TEST RUN operation will be started The 2 hours OFF TIMER will be set and the TEST RUN operation will be finished after 2 hours unit operation or by depressing the RUN STOP switch again 3 3 To end the test run wait for 2 hours or push RUN STOP switch again Number of The Unit 0 1 2 3 4 10 11 63 Timer Setting Display Left Two Digit 01 02 03 04 05 11 12 64 Re...

Страница 22: ...ity Low Pressure Thermistor Outdoor 31 System Incorrect Capacity Setting of Outdoor and Indoor Unit Incorrect Capacity Code Setting of Combination Excessive or Insufficient Indoor Unit Total Capacity Code outside of 80 120 35 Incorrect Setting of Indoor Unit No Duplication of Indoor Unit No In Same Ref Gr or The Connection Unit Number Exceeds The Maximum Number of Combination 38 Outdoor Unit Abnor...

Страница 23: ...rigerant Temperature Operating Mode Cool Discharge Gas Temperature Td Liquid Pipe Temperature Te 8 Check Pressure Discharge Pressure Pd MPa Suction Pressure Ps MPa 9 Check Voltage Rated Voltage V Operating Voltage L1 L2 V L1 L3 V L2 L3 V Starting Voltage V Phase Imbalance 10 Check Compressor Input Running Current Input kW Running Current A A 11 Is the refrigerant charge adequate 12 Do the operatio...

Страница 24: ...24 66MP1306 Printed in Philippines ...

Отзывы: