INVERTER-DRIVEN 

MULTI-SPLIT SYSTEM 
AIR CONDITIONERS 

Outdoor Units 

Installation

Maintenance Manual 

Models

 

RAM-200FPS(D) 

RAM-250FPS(D) 

RAM-270FPS(D) 

 

The manual make sure to transfer to the next step of construction, and finally the customer keep it. 
(Transportation and Handling) 

→ (Refrigerant Piping Work) → (Electrical Wiring) → (Test Run) → (Customer)

 

  

Important Notice 

●The air conditioner for general use. Food, animals and plants, precision machinery and preservation of works of art and other special purpose, 

please do not use. 

●Do not install in the following places. If you have gas and oil droplets exist around, it will cause fires and machine deformation, corrosion, 

damage. 

○Oil (including machine oil) of the droplets, oil gas and more places.    ○The sulfur gas and hot springs more places. 

●Do not install in the following places, it will cause corrosion. 

○Near the sea (in the salty environment).    ○An acid or alkaline environment. 

●When produce electromagnetic waves used in medical equipment places, please note that the air conditioner to prevent malfunction. 

○Do not install the outdoor unit where the electromagnetic wave is directly radiated to the electrical box. 
○Do not install the indoor unit, outdoor unit, controller and cable within approximately 3 meters from strong electromagnetic waves such as 

medical equipment.   

●Do not install in the animals or plants will be directly affected by the wind to the place, otherwise have adverse effects on plants and animals. 
●Use the wireless remote controller, since they will be affected by the lighting equipment, etc., resulting in the receiver to receive signals failed, 

therefore as far as possible away from the receiver and the lighting of more than 1m. 

  Safety Summary

 

Before installation, This is a "

 Safety Summary

 " in the content, be sure to read, for the correct installation. 

In this manual to note that the "      Danger"      Caution, when the installation error, it may lead to significant harm, particularly marked. 
Therefore, an important part of safety, please be sure to actually follow. 

When the installation is complete, and then test run, to confirm whether there is abnormal. Please follow the manual's instructions, using the 
method, maintenance method for illustration to customers, and the installation manual and operation manual by the customers really to keep. 

 

Definition for signal words

 

DANGER

Immediate hazards which

 will 

result in severe 

personal injury or death.

 

Enforcement matters

Machine with a ground terminal, the user 

must follow the instructions for ground work. 

Prohibitions. 

Enforcement matters

Indicating the general behavior 

(Non-specific object). 

             

About electrical works

               

 
 
 
 
 

DANGER

 

When perform electrical work , please have a qualified personnel. Please note that the construction is not completely by 
yourself, there will be occurred an electric shock. 

Perform electrical work according to Installation Manual and all the relevant regulation and standard. If the instructions are 

not followed, an electrical shock and fire may occur due to insufficient capacity and inadequate performance.   

The wiring between products, please use the specification wire. Select the wrong wire, it will cause fire or electric shock. 

Ensure that the wiring terminals are tightened securely with the specified torques. If not, generating fire or electrical shock at 

the terminals connection part may occur.   

Fix the cables securely. External forces on the terminals could lead to a fire. 

Use an ELB(Earth Leakage Breaker)

In the event of fault, there is danger of an electric shock or a fire if it not used.   

Due to electrical wiring, inspection work and open the service cover, completely turn off the power to implement in order to 

avoid electric shock. 

Check that the ground wire is securely connected. If the unit is not correctly grounded, it leads electrical shock. Do not 

connect the ground wiring to gas piping, water piping, lighting conductor or ground wiring for telephone.   

 
             

 

About installation

               

 
 
 
 

DANGER

 

 

When installation, make sure you follow the installation manual. If the instructions are not followed, it may result in a water 
leakage, electric shock or a fire. 

Please install the unit where is able to withstand the weight. Strength, and installation is not complete, the body may fall and 

cause injury. 

Please do not place flammable gas and have doubts about the place to the installation, it may cause fires and other 

accidents. 

Do not climb air conditioner, or place objects on top, so as to avoid falling damage. 

In case of refrigerant leakage occurs, please immediately turn off the fire source (such as: stoves and other appliances), 

remove the refrigerant on the ground, open the doors and windows to ventilation , and contact your service contractor. 

The indoor unit drain pipe do not directly into the drainage ditches. The biogas will be produced through the drain pipe into 

the indoor, resulting in poisoned phenomenon. 

66MP1306 

IMPORTANT: 

READ AND UNDERSTAND 
THIS MANUAL BEFORE 
USING THIS HEAT-PUMP 
AIR CONDITIONER. 
KEEP THIS MANUAL FOR 
FUTURE REFERENCE.

 

 

 

Содержание RAM-200FPS

Страница 1: ...y or death Enforcement matters Machine with a ground terminal the user must follow the instructions for ground work Prohibitions Enforcement matters Indicating the general behavior Non specific object About electrical works DANGER When perform electrical work please have a qualified personnel Please note that the construction is not completely by yourself there will be occurred an electric shock P...

Страница 2: ... system which all indoor units are operated simultaneously the total indoor unit capacity should be less or equal to the outdoor unit capacity For the system which all indoor units are not operated simultaneously the total indoor unit capacity is available up to maximum against the outdoor unit capacity 1 2 Operation temperature range Condition Item Air inlet temperature of outdoor unit Air inlet ...

Страница 3: ... shall be used with the flaring tube adjustment gasket 1mm Using the 1 2H pipe situation can not be processed R410A special flaring tool can be used directly in the R407C Flaring for Tubes Extrusion Adjustment Gauge not use Dimensional Control for Extrusion Portion of Tube after Flaring Pipe Bender Using the 1 2H pipe situation can not be processed Please use the elbow welding connection Bending E...

Страница 4: ...6 15 88 19 4 19 7 19 05 23 3 Can not be processed 1 2H material Please use the attached flare connecting pipe Pipe thickness selected With the design pressure changes the pipe thickness and material should also be changed Pipe Size Existent Type New Refrigerant R22 R407C R410A Thickness Material Thickness Material Thickness Material Φ6 35 0 6 O 0 8 O 0 8 O Φ9 53 0 8 O 0 8 O 0 8 O Φ12 7 0 8 O 0 8 O...

Страница 5: ...is a high level of oil mist salty air or harmful gases such as sulphur 12 Do not install the outdoor unit where the electromagnetic wave is directly radiated to the electrical box 13 Install the outdoor unit as far as at least 3 meters from the electromagnetic wave radiator Strong wind blowing directly against the product installation method Installed on the roof and no buildings surrounding and t...

Страница 6: ...ed 350 Above 300 Above 100 Above Front Side Note Must install the wind break cover plate Option and the both sides must be opened Note Must be opened on both sides A separate installation A row installation two more 350 Above 300 Below 350 Above 300 Below 1000 Above 350Above 1000 Above 100Above 350 Above Setting two sets situation 300 Below 100 Above 100Above 300 Below 1000 Above Front Side 350 Ab...

Страница 7: ...sealed A separate installation A row installation two more Front Side 50Above 100Above 700 Above Note Must install the wind break cover plate Option and the both sides must one side be opened at least With the unit rear side same direction 350 Above 700Above Note Must install the wind break cover plate Option and the both sides must be opened 700Above 350Above 150 Above 700Above 100 Above A separa...

Страница 8: ...t to withstand full weight of the outdoor unit 560 Hole 4 Φ16 x 23 5 Long Hole If ensure 170 dimension and without interference with foundation base it can be downward the piping work To avoid the unit vibration transmitted to the buildings if necessary to install anti vibration rubber Fixed Bracket Fielded supplied 21mm Below A After Cut Off Concrete Anchor Bolt Shelf Width 60 mm Standard Parts O...

Страница 9: ... easy to produce powder Cautions for refrigerant piping work for example 2 Piping Direction The pipe can be connected in four directions Convex Drain Connector Washer Base Drain Hole When installing pipe through the wall Secure a cap at the end of the pipe Hole of wall Attach a cap or vinyl tape Attach a cap or vinyl tape Attach a cap or vinyl tape Do not place the pipe directly on the ground Rubb...

Страница 10: ...lease make the gap of the upper A division remove part of piping In the unit s internal piping and wiring do not interfere with each other 2 3 Connection piping bending use the pipe bender 2 4 In order to metal plate s burrs does not hurt to wiring and piping Please use the insulation material Field supplied materials to protect them Open the service cover essentials 1 Please remove the left screw...

Страница 11: ...m Piping Length Actual Length L1 L2 l 3 100m Below Equivalent Length L1 L2 l 3 120m Below The Total Length L1 L2 l0 l1 l2 l 3 250m Below Maximum Lift between Outdoor Unit and Indoor Unit The outdoor unit is higher than that of indoor unit H 1 40m Below The outdoor unit is lower than that of indoor unit H 1 30m Below Between each indoor unit H 2 15m Below Maximum Piping Length Between Each Multi ki...

Страница 12: ...connected to the indoor unit be sure to use an optional parts of the multi kit pipe set in order to prevent the uneven distribution of the refrigerant and causing the unit s capacity reduction Do not connect using the connector 1 Line branch use the line branch pipe As shown below Main pipe The pipe between each multi kit pipe or the pipe between outdoor units to first multi kit pipe Main Branch T...

Страница 13: ... Correct Setting Wrong Setting First Main Branch Second Main Branch First Branch Second Branch Third Branch First Main Branch Second Main Branch First Branch Second Branch Third Branch X Wrong Outdoor Outdoor Outdoor Outdoor First Main Branch First Main Branch Second Main Branch Second Main Branch First Branch First Branch Second Branch Second Branch Third Branch Third Branch X Wrong Fourth Branch...

Страница 14: ...vibration of the piping Pay special attention in case of short piping length 4 Please perform the air tight test Connect the gauge manifold using charging hoses with a vacuum pump or a nitrogen cylinder to the check joints of the liquid line and the gas line stop valves Perform the air tight test Connect a manifold gauge to the check joints of the liquid and gas stop valves in the outdoor unit Do ...

Страница 15: ...nt R410A which directly touch refrigerant 3 If vacuum degree of 0 1MPa 750mmHg is not available it is considered that leakage exists Check for any gas leakage once again If no leakage exists operate the vacuum pump for one to two hours 5 4 The Additional Refrigerant 1 Outdoor unit has been filled with refrigerant but still based on the length of pipe filled with an appropriate amount of refrigeran...

Страница 16: ... will result in weight percent composition changes so can not directly add refrigerant treatment must be re processing system 5 6 Caution of Measure Pressure Data from The Check Joints Measure pressure data of work please from the check joints of gas line stop valve right figureⒶ and the check joints of piping line right figureⒷ to connect And then please according to the different operation state...

Страница 17: ...Supply 3Φ 60Hz Maximum Current A ELB Earth Leakage Breaker Power Switch Power Supply Size mm2 Earth Wire Size mm2 Transmission Cable Size Number of Poles Rating Sensitivity Current mA Rating Current A Switch Capacity A Fuse Capacity A 1 2 2 3 4 5 RAM 200FPS 230V 22 3 30 30 60 30 3 5 5 5 2 Core Shielded Twist Pair Cable 0 75mm2 Total Length 1000m Below RAM 250FPS 29 40 40 5 5 RAM 270FPS 37 100 50 1...

Страница 18: ...tion wiring construction The transmission cable of indoor and outdoor unit and the 220V power source cord be sure to keep the distance of more than 5 6cm Therefore do not use the coaxial cable If the transmission cable and power source cord connecting wrong will cause the PCB of the outdoor unit burning Please pay special attention 10 Indoor and outdoor unit s power source cord and connection wiri...

Страница 19: ...gs shall be attached the insulation tape or insulation sleeve Χ Ο Fold the wire and reserve for a maintenance operation the desired length Prevent need to remove the wiring plug for maintenance Cord Band Operation 1 When wire through the cord band appropriately tighten it as show below 2 Make sure the cord with high and low pressure sensor isolation 3 Tighten the cord to be isolated with pipe comp...

Страница 20: ...Do not input the power source to the terminal No 1 2 of transmission wiring 3 When power source wiring phase error the unit can not be operated and the remote controller display alarm code 05 At this time please refer to the electrical box caution nameplate check the phase of the first side and replace it The phase of the replacement work please process under the power source turn off 4 Does the o...

Страница 21: ... operation 3 2 Depress RUN STOP switch The TEST RUN operation will be started The 2 hours OFF TIMER will be set and the TEST RUN operation will be finished after 2 hours unit operation or by depressing the RUN STOP switch again 3 3 To end the test run wait for 2 hours or push RUN STOP switch again Number of The Unit 0 1 2 3 4 10 11 63 Timer Setting Display Left Two Digit 01 02 03 04 05 11 12 64 Re...

Страница 22: ...ity Low Pressure Thermistor Outdoor 31 System Incorrect Capacity Setting of Outdoor and Indoor Unit Incorrect Capacity Code Setting of Combination Excessive or Insufficient Indoor Unit Total Capacity Code outside of 80 120 35 Incorrect Setting of Indoor Unit No Duplication of Indoor Unit No In Same Ref Gr or The Connection Unit Number Exceeds The Maximum Number of Combination 38 Outdoor Unit Abnor...

Страница 23: ...rigerant Temperature Operating Mode Cool Discharge Gas Temperature Td Liquid Pipe Temperature Te 8 Check Pressure Discharge Pressure Pd MPa Suction Pressure Ps MPa 9 Check Voltage Rated Voltage V Operating Voltage L1 L2 V L1 L3 V L2 L3 V Starting Voltage V Phase Imbalance 10 Check Compressor Input Running Current Input kW Running Current A A 11 Is the refrigerant charge adequate 12 Do the operatio...

Страница 24: ...24 66MP1306 Printed in Philippines ...

Отзывы: