– 78 –
Inspection method 1
Insert the power source, and check to see that the
LED is on at electrical unit 1 or electrical unit 2.
Is the 25A fuse working normally?
Is the 5A fuse working normally?
Yes
Yes
Yes
Yes
No
No
No
No
LED on
LED off
The control P.W.B. is broken.
Replace the control P.W.B.
Is AC220~240V flow to the L/N (A/B) terminal?
Follow "Inspecting external electrical parts" and check
the cause of the problem.
Connect a commercial-use 220-240V power source
to the L/N (A/B) terminal.
Replace the broken part
and the 25A fuse.
The control power source is broken.
Replace the control P.W.B.
Is varistor 2 broken?
There is the possibility that an irregular voltage has been
flowing to the L/N (A/B) terminal. Check to see that the
power source is not abnormality.
Replace the 5A fuse and varistor 2.
Check to see that varistors 1-3,
diode stacks SPM2 are not
broken.
Содержание RAM-130QH5
Страница 10: ... 11 SIX ROOM SYSTEM MULTI R A C RAM 130QH5 CONNECTING POSISION TO BE ABLE TO INSTALL ...
Страница 20: ... 22 CAPACITY DIAGRAM RELATED TO THE PIPING LENGTH MODEL RAM 130QH5 ...
Страница 25: ... 29 6V01 ...
Страница 26: ... 31 ...
Страница 28: ... 35 ...
Страница 33: ... 41 Outdoortemperature STAROTP_C TSKTM1_C1 Outdoortemperature STAROTP_C TSKTM1_C2 ...
Страница 34: ... 43 ...
Страница 35: ... 45 ...
Страница 36: ... 47 ...
Страница 37: ... 49 ...
Страница 47: ... 59 5A ...
Страница 54: ... 66 ...
Страница 55: ... 67 5 Reversing valve control circuit Fig 5 1 ...
Страница 58: ... 70 8 Overload control circuit OVL control circuit Fig 8 1 Overload Control System Configuration Fig 8 2 ...
Страница 77: ... 92 TROUBLESHOOTING OF THE SYSTEM POWER MODULE ...
Страница 78: ... 93 ...
Страница 79: ... 94 ...
Страница 83: ... 98 ...
Страница 84: ...HITACHI PM NO 0000 Printed in Malaysia RAM 130QH5 ...