– 13 –
INSTALLATION
PIPE LENGTH
(1) Total 45m maximum pipe length for each refregrant cycle (upper cycle and lower cycle).
(2) Pipe length for one indoor unit : maximum 25m.
Hight Difference between indoor units should be not more than 5m
To the outdoor unit, up to three indoor units can be connected until the total value of
capacity from 5.0kW to 9.0kW for each refregrant cycle (upper cycle and lower cycle).
Make sure to connect to two or three indoor units for each refregerant cycle.
Indoor unit 5 Indoor unit 6
Indoor unit 4
Indoor unit 2 Indoor unit 3
Indoor unit 1
Outdoor unit
L1
L2
L3
Indoor unit 2 Indoor unit 3
Indoor unit 1
Outdoor unit
L4
L5
L6
Indoor unit 5 Indoor unit 6
Indoor unit 4
(L1 + L2 + L3) = (L4 + L5 + L6) = Maximum 45m
Minimum piping length for each indoor unit is 5m.
Maximum piping length for one indoor unit is 25m.
Содержание RAM-130QH5
Страница 10: ... 11 SIX ROOM SYSTEM MULTI R A C RAM 130QH5 CONNECTING POSISION TO BE ABLE TO INSTALL ...
Страница 20: ... 22 CAPACITY DIAGRAM RELATED TO THE PIPING LENGTH MODEL RAM 130QH5 ...
Страница 25: ... 29 6V01 ...
Страница 26: ... 31 ...
Страница 28: ... 35 ...
Страница 33: ... 41 Outdoortemperature STAROTP_C TSKTM1_C1 Outdoortemperature STAROTP_C TSKTM1_C2 ...
Страница 34: ... 43 ...
Страница 35: ... 45 ...
Страница 36: ... 47 ...
Страница 37: ... 49 ...
Страница 47: ... 59 5A ...
Страница 54: ... 66 ...
Страница 55: ... 67 5 Reversing valve control circuit Fig 5 1 ...
Страница 58: ... 70 8 Overload control circuit OVL control circuit Fig 8 1 Overload Control System Configuration Fig 8 2 ...
Страница 77: ... 92 TROUBLESHOOTING OF THE SYSTEM POWER MODULE ...
Страница 78: ... 93 ...
Страница 79: ... 94 ...
Страница 83: ... 98 ...
Страница 84: ...HITACHI PM NO 0000 Printed in Malaysia RAM 130QH5 ...