One to One (Method B: Power supply from the outdoor
unit)
●
One to One (Method C: Individual power supply for
indoor and outdoor unit)
●
One to Two/Four(Method B: Power supply from the
outdoor unit)
●
One to Two/Four(Method B: Power supply from the
outdoor unit)
Precautions
Install an ELCB at the No Fuse Breaker (NFB) or manual switch of the branch circuit marketed “
※
” near the packaged
A/C.
Use a high-sensitivity, high-speed (trip time < 0.1 second) ELCB of the required capacity for high frequency operation
(for inverter use).
“B” and “C” in the table below refer to “Method B” and “Method C”.
Mode/Shape
ELCB Rated
Current
(A)
Power SW
Wire Gauge (mm
2
)
Rated Current
(A)
Fuse Size
(A)
Power Cable
Indoor/Outdoor Connection
Wiring
B, C
Operation
Circuit
Indoor
Connection
Power Cable
Earth
Remote
Control
Cable
B
⑩
C
Outdoor
C
Indoor
B Power
Outdoor Unit
RAC-
Vol
tage
B
①
C
Outdoor
②
C
Indoor
③
B
④
C
Outdoor
⑤
C
Indoor
⑥
B
⑦
C
Outdoor
⑧
C
Indoor
⑨
<10
m
<20m
<20m <35m <50m <70m <75m
112/125/140/
160FPSQB
AC
1
Φ
230
V
60
Hz
50 50
5 60 60 30 35 35
5 8.0
8.0
8.0 2.0
2.0
2.0
2.0
2.0
3.5
Above
0.75
2.0 2.0
Above
0.75
●
ELCB Selection
Determine the rated current of the ELCB based on the total wiring
capacity shown in the right table.
Determine the ELCB model, sensed current, and trip current based
on the information shown in the right table.
*Use high-sensitivity, high-speed (trip time < 0.1 second) ELCB.
*Confirm the ELCB rated current, sensitivity, and trip time and
protective coordination of the upper part.
Rated Current
(A)
ELCB Mode (trip current)
Rated Sensed Current
(mA)
15, 20, 30
EX-30(5kA),
EX-50B(10kA),
EX-50C(35kA)
30
40, 50
EX-50B(10kA),
EX-50C(35kA)
30, 100
60, 75, 100
EX-100(10kA),
EX-100B(35kA)
100
Note
1.
Use high-sensitivity, high-speed ELCB with rated sensed current under 30mA or medium-sensitivity ELCB with rated
sensed current over 500mA. The trip time of both types must be within 0.1 second.
2.
Use high-frequency ELCBs for inverter use.
●
Select transformers according to the instructions below.
Transformer Capacity
≧
Maximum Wattage ×1.3
Determine maximum wattage as shown below:
Type RAM-112FPSQB
RAM-125/140/160FPSQB
Max. Current (A)
27
28
Outdoor unit
Indoor unit
Remote control
Remote Control
Indoor unit
Outdoor unit
Indoor unit
Indoor unit
Outdoor unit
Remote control
Remote controls
Indoor unit
Indoor unit
Outdoor unit