background image

11 

(4) Pipe connection and insulation 

1)

 

Make sure the interceptor valve of the outdoor unit is completely shut. 

2)

 

Connect the pipes between the indoor unit and the outdoor unit. When locking pipefittings, 
coat refrigeration oil on the interior and exterior edges of the flare and lock the fitting with two 
wrenches at the specified torque. Check leakage after locking. Fill pipes up with nitrogen 
before welding. 

3)

 

Fix the pipes between the indoor unit and outdoor unit appropriate. Avoid fixing pipes on 
weak wall surface and ceilings. This may cause vibration and noise, particularly for short pipe 
length. 

4)

 

Re-confirm there is no leakage after piping. 

5)

 

Wrap pipefittings with insulation sheets and pack with plastic tape for insulation. Also, wrap 
the gas inlet and liquid inlet of the refrigerant pipe with insulation sheets to ensure insulation.

 

Remark: Prepare refrigeration oil 

on-site.  

Supplier: JX Nippon Oil & Energy 

Corporation 

Type: Synthetic Ze-GLES RB74 

 

 

 

 

Interceptor valve on the outdoor unit 

 

 

Model 

RAM-112/125/140/160FPSQB
Gas Inlet 

Liquid Inlet 

Hex key (mm) 

Spool locking torque (N•m)

11~14 

7~9 

 

Interceptor valve on the indoor unit

 

Work with two wrenches

 
Locking torque table: 

Pipe size 

Torque 

Φ

 6.35 (1/4 ”) 

20 N•m 

Φ

 9.53 (3/8 ”)   

40 N.m 

Φ

 12.7 (1/2 ”)   

60 N.m 

Φ

 15.8 8 (5/8 ”)   

80 N.m 

 

  (5) Air-tightness test 

1)

 

Shut the interceptor valve spool of the gas and liquid inlets before running the air-tightness test. 

2)

 

Fill in air or non-flammable gas (except for oxygen and toxic gases) from the pipe union of the fluid inlet and the pipe union of 
the gas inlet to run the air-tightness test. The pressure is 4.15MPaG. Release gas after the test. 

  3-2 Evacuation and Refrigerant Filling 

(1) Evacuation 

1)

 

Please refer to the instructions on the attention plate inside the panel cover for details of interceptor valve operation. 

2)

 

Evacuate from both the gas and liquid interceptor valves until pressure is below -0.1MPaG (-750mmHg). 

3)

 

After evacuation, shut the valve on the manifold gauge set, stop evacuation, and settle for one hour to 

see if meeting reading 

rises. 

4)

 

As the pipe union does not fit in the cap nut, use a filling hose. Also, lock the cap nut at 15-16N•m afterwards. 

5)

 

Make sure to check leakage with a leakage detector and bubbles. Do not use bubble liquids containing NH

3

. Recommended 

bubble liquids for the leakage test tabulated below. Do not use general household detergents in the bubble test. 

(2) Refrigeration filling 

1)

 

The unit has been equipped with refrigerant before shipping. If pipes are longer than the design range, add suitable amount of 
refrigerant on-site (p. 12). 

2)

 

Fully open the gas interceptor valve. 

3)

 

The compressor operates when the air-conditioner is in operation. Add refrigerant from the pipe union of the fluid interceptor 
valve. At the same time, the fluid interceptor valve opens slightly. 

4)

 

Fully open the fluid interceptor valve after filling refrigerant. 

5)

 

Make sure to check leakage afterwards. 

Note 

1.

 

When removing the cap of the interceptor valve spool, gas will pop from the O-ring inside and thread, which is irrelevant to a gas 
leak. 

2.

 

As the outdoor unit uses R401A refrigerant, use the manifold gauge set and filling hose for R401A refrigerant. 

3.

 

When pressure does not drop below -0.1MPaG (-750mmHg) after evacuating for one hours, there may be leakage or water inside 
the pipe. First, check if there is leakage. Next, evacuate for one hour again. Lastly, check pressure again

Do not purge air inside the unit with refrigerant. This will result in refrigerant insufficiency and cause machine damage.

 

Recommended bubble liquids 

Bubble Liquid 

Manufacturer 

SNOOP NUPRO 

(USA) 

ギュポフレックス

 

Yokogawa & Co., Ltd. 
(Japan). 

 

Make sure to check refrigerant leakage. Mass refrigerant 
leakage will cause: 
1.

 

Oxygen insufficiency. 

2.

Toxic gas production in contact with heat.

 

Guidelines for Refrigerant Pipe Installation 

 

Gas piping 

Manifold 
gauge set 

Vacuum pump 

Nitrogen cylinder 
(for welding and air-tightness test)

Gas valve 

Liquid valve 

Liquid piping

Indoor Unit

 

Make sure to add insulation to the pipe 
union and cap nut. 

 

Make sure to add insulation to fluid 
pipes. 
(To prevent performance from 
deterioration due to external 
temperature influence and pipe surface 
condensation due to low pressure). 

Interceptor valve control of the liquid inlet.

Interceptor valve control of the gas inlet.

Do not work with two 
wrenches here to prevent 
refrigerant leakage.

Interceptor 
valve 

Cap nut

Insulation Sheet Wrapping 
Wrap the exterior with plastic tape 
(both the gas and fluid pipes must be 
wrapped with insulation sheets)

 

Содержание RAM-112FPSQB

Страница 1: ...nts may generate electromagnetic wave avoid causing malfunction of the air conditioner To prevent electromagnetic interference EMI do not point the electromagnetic wave emitting surface of medical instruments toward the electrical control panel remote controller and remote controller cable of the air conditioner To avoid EMI in the air keep machinery generating electromagnetic wave such as radios ...

Страница 2: ...geration oil with the special filling machine for R410A and Ze GLES RB74 may cause machine failure and even explosion or fire Make sure to use qualified refrigerant and refrigeration oil only The machine maintains a high pressure at all times Do not heat the machine or any parts in any situation This may cause machine failure and even explosion or fire Make sure to remove all flammable objects on ...

Страница 3: ...ench y 2mm larger than the Φ12 7 or Φ15 88 wrenches for use on R410A pipes Not suitable for use on the pipes of currently used refrigerants For locking cap nuts y Φ6 35 and Φ9 53 wrenches can also be used Welder y Weld pipes as instructed flame adjustment welding temperature and choice of welding materials For welding refrigerant pipes Nitrogen y Strictly prevent dust from entry Following the nitr...

Страница 4: ...7 0 8 O 0 8 O 0 8 O Φ15 88 1 0 O 1 0 O 1 0 O Φ19 05 1 0 O 1 0 O 1 0 1 2H Φ22 2 1 2 O 1 15 O 1 0 1 2H Φ25 4 1 2 O 1 0 1 2H 1 0 1 2H Φ28 6 1 4 O 1 0 1 2H 1 0 1 2H Φ31 75 1 4 O 1 1 1 2H 1 1 1 2H Φ38 1 1 65 O 1 15 1 2H 1 35 1 2H Connector Selection The wall thickness of connectors elbows and tubing must be changed according to the design pressure change As 1 2H parts cannot be bend or expanded select ...

Страница 5: ...and PSW3 switches on the mainboard of outdoor unit for three seconds 2 3 Outdoor unit installation 1 Installation space Retain maintenance space for the outdoor unit as shown below unit mm Standalone Standalone Standalone Two or More Units side by side No obstruction above No obstruction on sides and above Obstruction in front of the air outlet Even both sides are clear of obstruction maintain at ...

Страница 6: ... Do not install the unit at locations where strong wind may blow off the roof or wall Secure the unit with steel wire if necessary 2 Add rubber cushions to the four legs of the unit stand 3 The location should be convenient for draining rainwater and condensate from defrosting For good drainage the outdoor unit should be installed in places with draining facilities When installing under roofs wher...

Страница 7: ...ection A when using this type of anchor bolts Otherwise it will be difficult to remove the pipe cover 5 Securely fix the outdoor unit on the foundation to prevent collapse in a strong wind or an earthquake or noise due to loss of level leaning aside 6 When using ordinary frames whose legs are narrower than the legs of the outdoor unit add a board under the legs of the outdoor unit as shown in the ...

Страница 8: ... the indoor units 20 20 Max lapse height between indoor units H2 3 3 Max pipe length between branch pipes and indoor units L1 L2 10 10 Branch pipe selection MW NP282A at a Cautions 1 The length and route of both the refrigerant and refrigeration oil pipes must be the same 2 Branch pipes should be near the indoor unit 2 Refrigerant pipe size Indoor unit Outdoor unit Capacity Level Refrigerant Pipe ...

Страница 9: ... instructions below Operation Air Conditioner Pipe union Ⓐ on the gas interceptor valve Low pressure Pipe union Ⓑ on the liquid interceptor valve Filling refrigerant after evacuation or repair Note After removing the filling hose prevent refrigerant and refrigeration oil from contaminating the electrical panel Penetrating walls Protect pipe ends when penetrating walls Protect pipe ends with a cove...

Страница 10: ...ing the unit put back the pipe cover afterwards Wrap pipes with insulation sheets prepare on site before penetrating pipes through the cap hole to ensure it is seamless Make sure that there is adequate space for putting back the pipe cover Panel removal direction Rear piping Pipe cover Front piping Right piping Bottom piping cover y As shown in the left diagram pipes can be installed in four locat...

Страница 11: ...terwards 5 Make sure to check leakage with a leakage detector and bubbles Do not use bubble liquids containing NH3 Recommended bubble liquids for the leakage test tabulated below Do not use general household detergents in the bubble test 2 Refrigeration filling 1 The unit has been equipped with refrigerant before shipping If pipes are longer than the design range add suitable amount of refrigerant...

Страница 12: ...W additional refrigerant L l x P L Pipe length l Standard pipe length 30m P Compensational value 60g m Example L L0 L1 L2 25 6 3 34m L l 34 30 4m Additional quantity of refrigerant W L l x P 4m x 60 g m 240g 3 Fill in the additional quantity of refrigerant W calculated in 2 3 5 Recovering Refrigerant Follow the steps below to recover refrigerant from the outdoor unit before relocating the indoor a...

Страница 13: ...W5 1 ON is shown on the right diagram When more than two outdoor units are connected to the H LINK disabled the terminal impedance DSW5 1 OFF from the second outdoor unit onward Make sure that the terminal impedance of only one outdoor unit in the H LINK is ON When there is only one outdoor unit do not change the factory setting y Use the same type of cables for all units on the H LINK Located on ...

Страница 14: ...bove 0 75 2 0 2 0 Above 0 75 ELCB Selection Determine the rated current of the ELCB based on the total wiring capacity shown in the right table Determine the ELCB model sensed current and trip current based on the information shown in the right table Use high sensitivity high speed trip time 0 1 second ELCB Confirm the ELCB rated current sensitivity and trip time and protective coordination of the...

Страница 15: ... Type 3 method at impedance under 100Ω Ask a qualified electrician to implement the work 5 Make sure to disconnect power source before opening the electrical panel for wiring or service to prevent electric shock Warning When installing the panel cover avoid jamming wires together to prevent electric shock and fire L1 1 L2 2 N Upper Right Panel Cover Earth cable Main power cable Operation circuit c...

Страница 16: ...f there are abnormalities Press the Run Stop and CHECK buttons on the remote control at the same time for 3 seconds or longer Test Run and Connected No of Indoor Units will be shown on the LCD display When multiple units are connected check the total number of connected indoor units If the number of connected units shown on the LCD display is smaller than the actual number of connected units check...

Страница 17: ...igerant temperature Fluid pipe temperature ºC Compressor out temperature ºC 8 Refrigerant pressure Delivery pressure MPaG Intake pressure MPaG 9 Voltage Rated voltage V Operating voltage L1 N V L1 L2 V Start voltage V 10 Compressor input power and current Power kW Current A 11 Refrigerant filling level Correct Incorrect 12 Remote control functions Correct Incorrect 13 Protective device functions C...

Страница 18: ... Settings of each input terminal should be different The value of settings greater than the default value is invalid Not in use Not in use Heating Mode Operation Signal Cooling Mode Alarm Signal Stop Request Compressor ON Signal Force Stop Defrost Signal Current Control 60 Current Control 70 Current Control 80 Current Control 100 Input Setup 1 CN1 Code 1 2 Input Setup 2 CN1 Code 2 3 Input Setup 3 ...

Страница 19: ...t capacity mismatch Indoor unit capacity is 100 130 higher than the outdoor unit capacity 35 Indoor unit number setup error Repeated number setting or the number is greater than the connected number of indoor units 38 Protection check circuit error outdoor unit Error of the outdoor unit protection check circuit 41 Cooling overload high pressure switch activated When the outdoor unit protection act...

Страница 20: ...20 66MP1388 RAC AF D ...

Отзывы: