![Hitachi RAI-25NH5 Скачать руководство пользователя страница 54](http://html.mh-extra.com/html/hitachi/rai-25nh5/rai-25nh5_service-manual_139918054.webp)
– 64 –
TROUBLESHOOTING WHEN TIMER LAMP BLINKS.
Model RAI-25NH5, RAI-35NH5
Perform troubleshooting according to the number of times the indoor timer lamp and outdoor LD301 blink.
SELF-DIAGNOSIS LIGHTING MODE
Model: RAI-25NH5, RAI-35NH5
No.
Timer indicator flashing mode
Reason for display
Section of estimated fault
Four-way valve faulty
The room heat exchange
temperature is low during heating,
or it is high during cooling.
Outdoor unit forced operation
The outdoor unit is in forced
operation or undergoing balancing
after forced operation.
Indoor/outdoor interface faulty
The interface signal from the
outdoor unit has been interrupted.
Outdoor electrical assembly
defective.
Abnormal water level detection
All stop when the float switch has
been activated.
Drain pump forced operation.
When the knob of drain pump test
switch at Indoor P.W.B main slide to
‘test’ position.
Room thermistor or heat
exchanger thermistor is faulty
When room thermistor or heat
exchanger thermistor is opened
circuit or short circuit.
DC fan motor overcurrent detection
Overcurrent in indoor DC fan motor
has been detected.
IC401 data reading fault
There was error in the data read
from IC401
(1) Four-way valve faulty.
(2) Disconnection in heat exchange
thermistor (only during heating)
Service SW in outdoor electrical
parts turned ON.
(1) Indoor interface circuit
(2) Outdoor interface circuit
Please check at the outdoor
electrical led lamp blinking (LD301)
and refer to self diagnosis lighting
mode for outdoor unit.
(1) Drain stopped up
(2) Drain pump
(3) Float switch
(1) Indoor P.W.B. Main.
(1) Room thermistor
(2) Heat exchanger thermistor
(1) Indoor fan locked
(2) Indoor fan motor
(3) Indoor P.W.B. Main
IC401 faulty
<Cautions>
(1)
If the interface circuit is faulty when power is supplied, the self-diagnosis display will not be displayed.
(2)
If the indoor unit does not operate at all, check to see if the F-cable is connected or disconnected.
(3)
To check operation again when the timer lamp is blinking, you can use the remote control for operation
(except for mode mark 1).
1
2
3
4
5
6
7
8
9
( – – Lights for 0.5 sec. at interval of 0.5 sec..)
5
sec.
– – 7 times
– – – – – – 3 times
– – – – – – – – Once
– – – – – – – Twice
– – 9 times
5 sec.
5 sec.
5 sec.
5 sec.
5 sec.
1
– – 6 times
5 sec.
– – 4 times
5 sec.
– – 10 times
5 sec.
– – 13 times
5 sec.
Содержание RAI-25NH5
Страница 31: ... 29 MODEL RAI 25NH5 RAI 35NH5 WIRING DIAGRAM INDOOR UNIT ...
Страница 33: ...CIRCUIT DIAGRAM MODEL RAI 25NH5 RAI 35NH5 33 ...
Страница 36: ... 39 47 RAI 25NH5 RAI 35NH5 ...
Страница 58: ... 68 CHECKING THE REMOTE CONTROLLER ...
Страница 59: ... 69 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAI 25NH5 RAI 35NH5 17 18 13 2 4 8 14 3 1 5 12 6 7 15 ...
Страница 62: ...HITACHI PM NO 0271E Printed in Malaysia RAI 25NH5 RAI 35NH5 ...