LD301 blinks 12 times.
Fan lock error.
Is CN24 connected?
Is the propeller fan
locked?
Have the 1A fuse and
R107 blown?
Is +15V being generated?
Check voltage both between
CN18 3 and 6 on the main
P.W.B., and between +15V
and 15-0V (silk-screened) on
the main P.W.B.
Is the fan operating?
(An error occurs after the
fan operates for 2 minutes.)
Is the voltage between 4
and 6 at CN24 normal?
(Normally, the voltage is
above approx. DC1.7V.)
Connect the connector.
Remove any
obstructions.
Replace the fan motor
and main P.W.B.
Is the voltage between 4 and
7 at CN24 normal?
Check to see if the voltage is
within 2.5V 0.5V using a
tester.
(In effect, the output voltage
is alternately switched
between 5V and 0V.)
Replace the main
P.W.B.
Replace the fan motor.
Yes
No
No
No
Yes
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Содержание RAC-E08H2
Страница 17: ... 15 CONSTRUCTION AND DIMENSIONAL DIAGRAM MODEL RAS E08H2A RAS E10H2A INDOOR UNIT Unit mm ...
Страница 18: ... 16 CONSTRUCTION AND DIMENSIONAL DIAGRAM MODEL RAC E08H2 RAC E10H2 OUTDOOR UNIT ...
Страница 22: ... 20 CIRCUIT DIAGRAM MODEL RAS E08H2A RAS E10H2A ...
Страница 23: ... 21 RAC E08H2 RAC E10H2 MODEL ...
Страница 25: ... 23 ...
Страница 27: ... 25 ...
Страница 28: ... 26 ...
Страница 30: ... 28 ...
Страница 31: ... 29 ...
Страница 47: ... 45 ...
Страница 48: ... 46 ...
Страница 50: ... 48 ...
Страница 51: ... 49 ...
Страница 52: ... 50 ...
Страница 54: ... 52 ...
Страница 71: ... 69 SELF DIAGNOSIS LIGHTING MODE MODEL RAC E10H2 SELF DIAGNOSIS LIGHTING MODE MODEL RAC E08H2 RAC E10H2 ...
Страница 77: ... 75 ...
Страница 81: ... 79 ...
Страница 82: ... 80 ...
Страница 83: ... 81 ...
Страница 92: ... 90 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAS E08H2A RAS E10H2A ...
Страница 94: ...THE UPDATED PARTS LIST FOR THIS MODEL IS AVAILABLE ON ESTA ...
Страница 95: ...HITACHI RAS E08H2A RAC E08H2 RAS E10H2A RAC E10H2 SM0026 ...