– 73 –
2. Indoor fan does not operate (others are normal)
Can the fan be stopped by remote
control?
The microcomputer fan PWM
output (at pin ) is 1-5V.
Replace the microcomputer.
Replace the fan motor.
Replace the microcomputer.
Perform final operation check.
3. Air deflector does not move (others are normal)
Are pulse signals output at
microcomputer pins - when
auto swing is turned on in the fan
mode?
Replace the microcomputer.
Is a voltage over 15 or below 10V
being generated on the 12V line?
Replace IC111.
Yes
Yes
Yes
Yes
No
No
No
No
Check IC711. If it is normal,
replace the air deflector motor.
Perform final operation check.
24
15
18
Содержание RAC-E08H2
Страница 17: ... 15 CONSTRUCTION AND DIMENSIONAL DIAGRAM MODEL RAS E08H2A RAS E10H2A INDOOR UNIT Unit mm ...
Страница 18: ... 16 CONSTRUCTION AND DIMENSIONAL DIAGRAM MODEL RAC E08H2 RAC E10H2 OUTDOOR UNIT ...
Страница 22: ... 20 CIRCUIT DIAGRAM MODEL RAS E08H2A RAS E10H2A ...
Страница 23: ... 21 RAC E08H2 RAC E10H2 MODEL ...
Страница 25: ... 23 ...
Страница 27: ... 25 ...
Страница 28: ... 26 ...
Страница 30: ... 28 ...
Страница 31: ... 29 ...
Страница 47: ... 45 ...
Страница 48: ... 46 ...
Страница 50: ... 48 ...
Страница 51: ... 49 ...
Страница 52: ... 50 ...
Страница 54: ... 52 ...
Страница 71: ... 69 SELF DIAGNOSIS LIGHTING MODE MODEL RAC E10H2 SELF DIAGNOSIS LIGHTING MODE MODEL RAC E08H2 RAC E10H2 ...
Страница 77: ... 75 ...
Страница 81: ... 79 ...
Страница 82: ... 80 ...
Страница 83: ... 81 ...
Страница 92: ... 90 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAS E08H2A RAS E10H2A ...
Страница 94: ...THE UPDATED PARTS LIST FOR THIS MODEL IS AVAILABLE ON ESTA ...
Страница 95: ...HITACHI RAS E08H2A RAC E08H2 RAS E10H2A RAC E10H2 SM0026 ...