– 92 –
1. Switch OFF main power supply.
2. Short circuit between JW001 and JW002.
3. Switch ON main power supply – LD302 will blink 1 time.
4. (Within 3 minutes) Press Test/Service Switch for 1 second or more.
5. Self-diagnosis result will be shown – LD303 will ON (LIT) and LD301 will be blinking. Then refer to diagnosis
table 2.
6. Switch OFF main power supply. Then release back JW001 and JW002 to original condition (no short
circuit condition).
*
If step No. 6 is not carried out, the system will not operate properly until 3 minutes has lapsed after
restore the power supply.
In case of service person forgot to release JW001 and JW002 to original condition;
Case 1:
If main power supply continuously ON, outdoor microcomputer will keep showing diagnosis result (LD303 will
ON and LD301 will blinks).
Case 2:
If main power supply OFF at once, then switch ON again:
a) Outdoor microcomputer will wait the self check command (by pressing test/service switch) within 3 minutes
(LD302 blinks 1 time).
If test/service signal input is not received, unit will return to normal operation mode after this 3 minutes has
lapsed. (LD302 OFF and LD301 blinks 1 time).
Case 3:
If main power supply OFF at once, then switch ON again and on indoor unit by remote control;
a) Indoor unit will receive remote control signal and send signal to outdoor unit. For the first 3 minutes, outdoor
micro-computer will ignore this indoor signal (LD302 blinks 1 time).
b) After 3 minutes has lapsed (LD302 OFF and LD301 blinks 1 time), unit will return to normal operation mode.
Содержание RAC-70YH7
Страница 35: ... 35 CIRCUIT DIAGRAM Remote Control ...
Страница 36: ... 37 CIRCUIT DIAGRAM MODEL RAS 70YH7 ...
Страница 37: ... 39 CIRCUIT DIAGRAM MODEL RAC 70YH7 ...
Страница 39: ... 42 MODEL RAC 70YH7 P W B MAIN ...
Страница 40: ... 43 P W B IPM BOARD P W B NF BOARD ...
Страница 41: ... 44 BLOCK DIAGRAM MODEL RAS 70YH7 RAC 70YH7 1ø 50 60Hz 220 240V AX 8X10 FM Outdoor DC Fan Motor ...
Страница 42: ... 45 51 53 53 55 57 49 29 66 23 25 25 25 25 ...
Страница 46: ... 53 ...
Страница 56: ... 66 220 240 220 240 3 15A RAC 70YH7 ...
Страница 57: ... 67 AC220 240V DC260 360V ...
Страница 58: ... 68 C001 C007 C015 C016 C026 C027 L004 L005 J25 J25 J25 J23 J58 J25 ...
Страница 60: ... 70 ...
Страница 61: ... 71 ...
Страница 62: ... 72 3 15A Fuse ...
Страница 63: ... 73 3 15A 3 15A DC260 360V ...
Страница 66: ... 76 ...
Страница 67: ... 77 ...
Страница 68: ... 78 TROUBLE SHOOTING ...
Страница 69: ... 79 DISCHARGE PROCEDURE AND METHOD TO STOP ENERGIZE THE POWER CIRCUIT ...
Страница 70: ... 80 ...
Страница 75: ... 85 2 Outdoor unit does not operate but receives remote infrared signal ...
Страница 80: ... 90 AC220 240V AC240V P W Bs P W Bs Replace outdoor P W B Main P W Bs ...
Страница 81: ... 91 Replace outdoor P W B Main Replace fan motor Replace outdoor P W B Main ...
Страница 83: ... 93 ...
Страница 84: ... 94 ...
Страница 86: ... 96 CHECKING THE REMOTE CONTROLLER ...
Страница 92: ...PM NO 0465E Printed in Malaysia RAS 70YH7 RAC 70YH7 ...