Connecting the pipe to the indoor unit

Remove the  are nut and seal cap.

By loosening the  are nut at the pipe end, the refrigerant is discharged in a small amount. The arrangement 
has been made for shipment, and the discharge of refrigerant is never a trouble to the equipment.

When the  are nut is removed, never fail to remove the seal cap. If not removed, the refrigerant will not be 
circulated, which result the compressor drive motor will possibly be burnt. 

Apply refrigerator oil to the union and the  ared portion of the pipe.
Wrap  are insulation, bind top and bottom  are insulation by binder.

  Connecting the pipe

  Drain Piping

5

6

!

CAUTION

When connecting pipes, if  are nut is over-tightened at the small diameter side, the screw thread of the service 
valve may be broken making pipe connection impossible. Be sure to tighten the nut with speci ed  torque.

Connecting of drain pipe

O

 Securely glue connection part of drain hose and PVC pipe, using PVC adhesive.

O

 If gluing of drain hose and PVC pipe is too weak, water leakage may occur.

  Be sure to wrap generally-available insulator (10mm or more of foamed polyethylene) around drain 

hose, inside the house, for insulation heat.

O

 Checking drain and water leakage. Perform after connecting power.

O

 If checking of drainage is omitted, water drop may occur.

O

 Add water to water pan of indoor unit as shown below.

O

 Perform test running of drain pump to check drainage operation.

O

 Test run method

1 Turn power on.
2 Remove cover of electric box and set the drain pump test run switch to TEST.
3 After checking the drainage, return the switch to NORMAL.

O

 If drain pump test run is set to TEST, drain pump may malfunction.

!

CAUTION

O

 The rubber strap used for  xing the insulator should 

not be tied with great force. Otherwise, this will damage 
heat insulation and causes water condensation.

!

CAUTION

O

 Insulate the refrigerant pipes as shown in Fig. 5.2.

Fig. 5.2 Insulation on 

O

 Position of piping connection is shown in Fig. 5.1. (Indoor Unit)

Fig. 5.1 Position of Piping Connection

8

9

11

O

 Do not create an upper-slope or rise for the drain piping, since drain water can  ow back to the indoor unit 

and leakage into the room will occur when the system operation is stopped.

O

 Do not connect the drain pipe with sanitary or sewage piping or any other drainage piping.

  When the common drain piping is connected with other indoor units, the connected position of each indoor 

unit must be higher than the common piping. The pipe size of the common drain pipe must be large enough 
according to the unit size and number of units. 

O

 After performing drain piping work and electrical wiring, check to ensure that water  ows smoothly as in the 

following procedure.

O

 Checking with the Float Switch

  (A)  Switch ON the power supply.

  (B)  Pour 1.5 to 2.0 liters of water into the drain pan.

  (C) Check to ensure that the water  ows smoothly or whether no water leakage occurs.

   

When water cannot be found at the end of the drain piping, pour another 1.5 to 2.0 liters of water into 

  

the drain.

  (D) Switch ON the power supply and press the RUN/STOP button.

!

CAUTION

O

 In case of pouring water through the access door.

O

 In case of pouring water through the air outlet.

(1) The position of the drain pipe connection is shown in  
 Fig. 

6.1.

Fig. 6.1 Position of Drain Pipe Connection

(2)  Prepare a polyvinyl chloride pipe with a 32mm outer 

diameter.

(3) Connecting Drain Piping

    

O

Insert the drain hose to the end of the drain pipe 

connection fully and fasten the hose with hose 
band (Accessory).

    

O

  Insulate the drain hose and band using the packing 

(5Tx50x200, 5Tx270x270): Accessory)

    

O

  The drain piping must be performed with a down-

slope pitch of 1/25 to 1/100.

    

O

  Completely fasten the tubing to the drain hose with 

the adhesive agent to avoid the drainage leakage.

* The total length of a+b+c shall be within 1,100mm. 

The drain hose must be performed with a 
horizontal or upper-slope to prevent the airpocket 
inner the hose. If the airpocket occurs, the drain 
water will  ow back to the unit and the abnormal 
noise and leakage to the room will occur when 
the unit is stopped.

P

(a)  Use the factory-supplied Drain Hose and Hose 

Band.

(b)  Do not apply excessive force to the Drain Pipe 

connection. It could cause a damage.

(c)  Do not use a bent or twisted Drain Hose. It will 

cause water leakage.

(d) Insert the factory-supplied Drain Hose completely. 

If not, or twisted, it will cause water leakage.

7

6

*  In case of lifting the drain pipe at the outlet part, 

perform the drain piping work as shown in the 
above  gure.

Fig. 6.2 Drain Piping

(4)  Insulate the drain pipe after connecting the drain 

 hose.

Packing (5Tx270x270)
(Accessory)

12

13

Wrap up the drain hose
completely to cover the 
hose band

Packing 

(5Tx50x200)

(Accessory)

Completely wrap up 
the transparent area
of the drain pipe
end connection.

Hose Band (Accessory)

Drain Piping
Connection

1/25 to 1/100 Down-Slope

Min. 100mm

This drain pipe shall be
separating from other pipes.

Common Drain Piping

Upward Slope

Unit

Rising Part

(Incorrect)

Twisted, incompletely insertion

Hose Band (Accessory)

Tightening Torque:
2.5 to 3.4N-m

Fully insert the hose to the end
of the drain pipe connection.

Drain Pipe
Connection

Drain Hose
(Accessory)

20+5

Use Vinyl Chloride
Type Adhesive

Elbow or
Vinyl Chloride VP25
(Field-Supplied)

(Correct)

Insert the end of hose
between heat exchanger
and drain pan.

Drain Pan

Pump

Water (1500cc to 2000cc)

Access Door

Insert the end of hose
between heat exchanger
and drain pan.

Pump

Water (1500cc to 2000cc)

840 (Unit)

Liquid Pipe Connection

Gas Pipe Connection

180 (Liquid Pipe)

110 (Gas Pipe)

127

(Liquid Pipe Connection)

102

(Gas Pipe Connection)

840 (Unit)

(mm)

18 (Gas Pipe)

25 (Liquid Pipe)

Union

Flare nut

Torque
wrench

Wrench

Pipe

Rubber strap tied with great force

Insulation for Refrigerant Pipe
(Accessory)

Cord Clamp
(Accessory)

Refrigerant Pipe

(Field-Supplied)

Insulation for Refrigerant Pipe

(Field-Supplied)

Insulation Material

(Factory-Supplied)

Unit
Side

Normal

Test

Drain Pump
Test SW

Drain Hose

Horizontal or Upper Slope

Hose Band (Accessory)

a (Max. 300mm)

c (Max. 50mm)

1/25 to 1/100
Down-Slope

Drain Hose (Accessory)

Max. 

850mm

INDOOR UNIT

(EN) INS RCI-30MH1 (4).indd   2

7/19/10   11:33 AM

Содержание RAC-30MH1

Страница 1: ...circuit breaker or fuse the danger of electric shock exists A main switch with a contact gap of more than 3 5mm has to be installed in the power supply line to the outdoor unit O Piping shall be suitable supported with a maximum spacing of 1m between the supports O Do not install the unit near a location where there is ammable gas The outdoor unit may catch re if ammable gas leaks around it O For ...

Страница 2: ...e drain piping pour another 1 5 to 2 0 liters of water into the drain D Switch ON the power supply and press the RUN STOP button CAUTION O In case of pouring water through the access door O In case of pouring water through the air outlet 1 The position of the drain pipe connection is shown in Fig 6 1 Fig 6 1 Position of Drain Pipe Connection 2 Prepare a polyvinyl chloride pipe with a 32mm outer di...

Страница 3: ...nnector Wall recessed wiring installation Supplied 0 50 gap Inside top wiring installation Alternative Wires Wires Lead wires 3 strands Lead wires connector Wiring installation illustrations When the wires to be connected from the inside top portion of top casing 1 Break off a perforated aperture located at the top portion of the bottom casing by nipper Smoothen the aperture by cutter 2 Fix the bo...

Страница 4: ...the band put the connecting cords in the band and snap it Loose the band put the connecting cords in the band and snap it Connecting cords Removal Of Air From The Pipe And Gas Leakage Inspection Gas Leakage Inspection Please use gas leakage detector to check if leakage occurs at the connection of Flare nut as shown on the right If gas leakage occurs further tighten the connection to stop leakage P...

Отзывы: