13ー11
< Troubleshooting by using the self-diagnosis memory function>
· By using the self-diagnosis memory function, you can check the failure mode (
1) occurring in the outdoor electrical
parts on the indoor unit side.
Steps
1. Clear the troubleshooting data.
2. Run the product for several minutes under the conditions where the compressor runs.
3. Redisplay and check the data written in the self-diagnosis memory.
· The self-diagnosis memory function can also be used to catch sporadic failure phenomena.
Steps
1. Clear the troubleshooting data.
2. Have the user use the product as usual until a failure phenomenon occurs.
(The period depends on the incidence of the phenomenon.)
3. At a later date, redisplay and check the data written in the self-diagnosis memory.
· For the outdoor self-diagnosis display (OH thermistor heat-up, overload lower limit cut) stemming from the freezing cycle
or operating condition, the time lag is long from operation startup to the emergence of the phenomenon.
Moreover, it is affected by the temperature, sunshine, operating hours, and other factors of the day, so that the
phenomenon may not be able to be identified at the time of a repair service visit. In that case too, use the self-diagnosis
memory function (
2).
· The outdoor self-diagnosis display "overload lower limit cut" and "OH thermistor heat-up" can be identified only when you
are using the self-diagnosis lamp of the outdoor unit and the self-diagnosis memory function of the indoor unit.
Note that this will not be automatically displayed on the indoor unit side.
Initiating troubleshooting
Yes
Perform troubleshooting according to the
self-diagnosis display.
No
No
No
No
Are the "timer lamp" (orange) of the indoor unit
blinking?
The product will begin to run in response to a remote
control setting: "cooling mode, temperature setting 16
"
(summer) or "heating mode, temperature setting 32
"
(winter).
Has the "operation lamp" been turned on?
s
e
Y
s
e
Y
Yes
Check the indoor electrical parts.
Is the compressor running?
Turn off the power and turn on the power and
press the "forcible cooling" switch to operate the
product.
Has the compressor started to run?
Check the freezing cycle.
Check the outdoor electrical parts.
Diagnosis and troubleshooting of indoor electric parts, outdoor electric parts and refrigerating cycle
Содержание RAC-25FXB
Страница 38: ...RAC 25 35FXB MODEL 6ー2 ...
Страница 39: ...RAC 50FXB MODEL 6ー3 ...
Страница 65: ...11ー6 10 10 10 10 10 R901 R904 R641 R907 R908 R694 R902 R695 R741 R740 R642 DSW1 DSW1 R903 R905 R906 ...
Страница 68: ...11ー9 L N 300 330 A B Main parts C021 C023 500 450V RAC 25 35FXB MODEL ...
Страница 72: ...11ー13 5 5 1 10 11 12 74 74 70 70 74 75 5 1 HIC P W B 74 70 75 ...
Страница 74: ...11ー15 2A Fuse DC300 330V 7 7 1 ...
Страница 75: ...11ー16 2A DC300 330V ...
Страница 76: ...11ー17 L N 300 330 A B MODEL RAC 50FXB ...
Страница 77: ...11ー18 300 330 C021 C023 500 450V 16V R249 33 ACT IP CUT 30 ...
Страница 81: ...11ー22 5 5 1 74 74 70 70 74 75 5 1 HIC P W B 40 41 42 74 70 75 ...
Страница 83: ...11ー24 2A Fuse DC300 330V 7 1 7 ...
Страница 84: ...11ー25 2A DC300 330V ...
Страница 94: ...13ー7 91 ...
Страница 95: ...13ー8 IC531 IC531 IC531 ...
Страница 96: ...13ー9 SELF DIAGNOSIS LIGHTING MODE RAC 25 35FXB MODEL ...
Страница 97: ...13ー10 SELF DIAGNOSIS LIGHTING MODE RAC 50FXB MODEL ...
Страница 119: ...14ー1 40 ...
Страница 120: ...14ー2 Please set the DIP switch No 6 to ON accordingly Refer to page 59 ...
Страница 121: ...14ー3 59 ...
Страница 122: ...14ー4 ...
Страница 131: ...Printed in Japan HRT TC NO 0842E RAF 25RXB RAC 25FXB RAF 35RXB RAC 35FXB RAF 50RXB RAC 50FXB ...