In case of P-GP160NAPU
1
The air panel has the wiring connectors (1) to (5) shown in
the right figure. Remove the tape that secures the wiring
connector and pull out the wiring connector.
2
Connect each wiring to the connector on the PCB inside the
electrical box of the indoor unit at the position shown below.
Make sure to pass the wirings through the cable band as
shown in the figure below.
3
After connecting the connector, tighten the cable band to
secure it.
?
N O T E
In case of attaching this air panel on the RCI-FSR series indoor unit,
remove the relay wiring attached to indoor unit PCB. After that, connect
the wiring attached to the air panel directly to the PCB as described above.
PCB
CN5
CN6
CN17
CN34
Cable
band
(3) Wiring for
PCB on air panel
(communication)
(3) Wiring for PCB on air
panel (communication)
(2) Wiring for motor of
elevating grille
(2) Wiring for motor
of elevating grille
(1) Wiring for
louver
(1) Wiring for louver
(5) Wiring for PCB on
air panel
(Power supply)
(5) Wiring for PCB on
air panel (Power supply)
(4) Earth wiring
(4) Earth wiring
Electrical
box
15.1 DIP SWITCH SETTINGS
Make sure to turn ON the No.3 pin of DSW9 for optional function
setting.
DSW9
ON
ON
1 2 3 4 5 6
0
98
7
1 2 3 4 5 6
6 5 4
32
1
0
98
7 6 5 4
32
1
ON
1 2 3 4
PCB on indoor unit
DSW9 (Optional function setting)
Turn ON the No.3 pin
?
N O T E
• Make sure to set the DIP switch. If it is operated without setting, the
opening and closing angle of the louver will be different. It may cause
dew condensation.
• All indoor and outdoor units must be shut down prior to attempting to
make DIP Switch adjustments, otherwise, the settings will not take
effect.
16 TROUBLESHOOTING FOR ELEVATING GRILLE
Phenomenon
Cause and Action
The air inlet
grille cannot
be moved
After Power Failure
Restart the operation. If a power failure occurs while the elevating grille is descending, it will be stored once in
the decorative panel for protection even if the descending operation is performed after the power is restored.
After that, normal operation is possible.
There is slack in the
suspension wire
If slack occurs in the suspension wire, it will be stopped forcibly. Correct the slack in the suspension wire.
Refer to "Countermeasure for Slack of Suspension Wire" in Section 3.
The air inlet grille cannot be
stored
This might occur when there is something on the air inlet grille or when the air filter is not installed properly.
Remove the placed object and install the air filter properly.
After the air inlet grille is stored,
it goes down once and then goes
up again
This is an automatic operation when the air inlet grille is not stored correctly. It is not abnormal.
The air inlet grille tilts up and
down
A little tilt is not abnormal. This is because there is a gap in the winding of the four suspension wires. If it is
extremely inclined (more than 30°), the elevating mechanism may be defective. Contact your contractor or
distributor.
"UPDW" on LCD Flashing
This might occur when the air inlet grille is not properly stored. Operate the elevating grille again and store the
air inlet grille in the correct position.
Sound during lifting operation
This is the drive sound of the elevating mechanism. It is not abnormal.
TROUBLESHOOTING FOR ELEVATING GRILLE
PMML0568 rev.0 - 01/2021
18