7 Commissioning
Checks prior to the test run
SMGB0099 rev.0 - 12/2016
235
7
13 The operating temperature:
• Cooling operation
a. Indoor DB 21.5 ºC and higher.
b. Indoor WB 16 ºC and higher.
c. Outdoor DB 0 ºC and higher.
• Heating operation
a. Indoor DB27 ºC and below.
14 Use shielded cables for the installation to avoid electrical noise. This must be less than 1000 m in length and meet
with national and local regulations.
15 Disconnect the KPI unit if it is connected to the indoor unit control. Otherwise the unit will not carry out the test run.
7.1.3 PC-ARFPE remote control
(1) Turn ON the power supply for all the indoor units.
(2) For the models with the auto-address function, wait for 3 minutes approximately. The addressing is automatically
performed. (There is a case that 5 minutes is required according to the setting condition.) After that, select using
language from “Menu”. Refer to the operation manual for details.
(3) Press and hold “ ” (menu) and “ ” (return) simultaneously for at least 3 seconds.
Test run screen
a. The test run menu will be displayed.
ADJ
/
OK
Test Run Menu
Test Run
Function Selection
Thermistor Selection
Input/Output
Function 5
01
03
ENT.
RTN.
SEL.
b. Select “Test Run” and press “OK”. The test run settings will be displayed.
Test Run Setting: 2 units
MODE
SPEED
MED
LOUV.
SEL.
ADJ
T-RUN TIME 120MIN
COOL
RTN.
RUN
?
N O T E
When “00” is indicated, the auto-address function may be performing. Cancel “Test Run” mode
and set it again.
Test Run Setting: 00 unit
MODE
SPEED
MED
LOUV.
SEL.
ADJ
T-RUN TIME 120MIN
COOL
RTN.
RUN
(4) The total number of the indoor units connected is indicated on the LCD (liquid crystal
display). The case of the twin combination (one (1) set with two (2) indoor units) is
indicated “2 units”, and the triple combination (one (1) set with three (3) indoor units) is
indicated “3 units”.
Test Run Setting: 2 units
MODE
SPEED
MED
LOUV.
SEL.
ADJ
T-RUN TIME 120MIN
COOL
RTN.
RUN
a. If the indicated number is not equal to the actual connected number of indoor unit, the auto-address function is
not performed correctly due to incorrect wiring, the electric noise or etc. Turn OFF the power supply and correct
the wiring after checking the following points; (Do not repeat turning ON and OFF within 10 seconds.)
-
Power supply for indoor unit is not turned ON or incorrect wiring.
-
Incorrect connection of connecting cable between indoor u nits or incorrect connection of controller cable.
-
Incorrect setting of rotary switch and dip switch (the setting is overlapped) on the indoor units PCB.