6 Optional functions
Optional functions through Remote control
SMGB0099 rev.0 - 12/2016
211
6
Elem.
Optional function
Individual
setting
Settings
Setting conditions
Description
C7
Release Compressor 3
min OFF Guard
O
00
Activated function
Function available depending on the
settings in b3.
01
Not activated function
C8
(7)
Selection of the
thermistor of remote
control switch
O
00
Not available (Suction thermistor)
This function determines the
thermistor to control the air
temperature.
01
Air temperature control using the
remote control thermistor
02
Air temperature control using
the average value of the air inlet
thermistor and the remote control
thermistor
S Remote Control / 2
Remote Sensor Selection
is connected
Models
RPI-FSN3(P)E
RPC-FSN3E
RPF(I)-FSN2E
RCI-FSN4
RPC-FSN3
O
00, 01,
02
Air temperature control using
remote sensor
Remote Sensor Selection
is connected
Models
RPK-FSN3M
00, 01,
02
Air temperature control using
the average value of the air inlet
thermistor and the remote control
thermistor
Remote Sensor Selection
is connected
Models
RPI-FSN4E
RPIM-FSN4E(-DU)
RCD-FSN3
RCIM-FSN4(E)
00, 02
Air temperature control using
the average value of the air inlet
thermistor and the remote control
thermistor
00,01
Air temperature control using
remote sensor
C9
Not available
–
“- -”
permanent Not available
CA
Not available
–
“- -”
permanent Not available
–
Cb
Selection of forced
stoppage logic
X
00
Forced stoppage input: A contact
This function determines the logic
operation for the forced stoppage
contacts.
01
Forced stoppage input: B contact
CC
Not available
–
00
Not available
Use at 00 conditions
–
01
–
Cd
Not available
O
00
Not available
Use at 00 conditions
01
CE
Fan stop at heating
thermo-off
O
00
Air flow volume: Low
01
If C8 setting 00: Slow
If C8 setting 01 or 02: fan operation stops
CF
Modification of Louver
Swing Range
Series
RCI, RPC, RCD, RPK
O
00
Standard (7 steps)
This function adjusts the angle of the
air outlet louver.
01
Cold draft prevention
(5 steps)
(Lower 2 steps cut off)
02
High ceilings
(5 steps)
(3)
(Higher 2 steps cut off)
d1
Power supply
ON/OFF 1
O
00
Not activated function
This function stores the unit settings
in the event of a power cut. The unit
is restarted when the power is re-
established.
01
Activated function
d2
Not available
X
“- -”
Permanent Not available
–
d3
Power supply ON/OFF 2
O
00
Not activated function
This function is used to restart the
unit after a power cut taking more
than 2 seconds.
01
Activated function