6 Optional functions
Optional functions through Remote control
SMGB0099 rev.0 - 12/2016
212
Elem.
Optional function
Individual
setting
Settings
Setting conditions
Description
d4
Cooling air temperature
drop prevention.
Models,
RPI-FSN3(P)E
RPC-FSN3E
RPF(I)-FSN2E
RCI-FSN4
RPC-FSN3
RPK-FSN3M
RPI-FSN4E
RPIM-FSN4E(-DU)
O
00
Not activated function
This function changes the cooling
operating conditions to avoid cold
draughts.
Not available for models
RCD-FSN3
RCIM-FSN4(E)
(Use as 00 conditions)
01
Activated function
d5
Prevention of decrease
of heating discharge air
temperature
O
00
Not activated function
This function prevents a drop in the
air temperature by decreasing the fan
speed, apart from the settings on the
remote control.
01
Activated function
d6
Room temperature
control for energy saving
O
00
Not activated function
This function saves energy when the
outdoor temperature is lower than the
air conditioning charge.
Function of the outdoor unit
Not available for models
RCD-FSN3
RCIM-FSN4(E)
(Use as 00 conditions)
01
Activated function
d7
Econofresh: OA Damper
minimum opening
O
00
6º
This function is used to set the fresh
outdoor air damper minimum opening
selection.
01
12º
02
18º
03
24º
04
30º
05
36º
06
42º
07
48º
E1
Econofresh cooling mode
O
00
Standard Process
This function allows to the outdoor
air damper to be opened in All Fresh
Operation mode. This mode able to
fully open the outdoor air damper
(according to the control system)
01/02
All-fresh
E2
Econofresh enthalpy
sensor
O
00
Not activated function
This function selects the enthalpy
sensor input.
01
Activated function
E3
Not available
O
00
Not available
Use at 00 conditions
–
01
E4
Econofresh: CO2 sensor
O
00
Standard
This function selects the CO2 gas
sensor input.
01/02
CO2 sensor
E5
Not available
O
00
Not available
Use at 00 conditions
–
01
E6
Indoor fan operation time
after cooling operation
stoppage
O
00
Not activated function
This function prevents the
condensation accumulation in the unit
by keeping the fan running after it is
switched off.
01
60 minutes
02
120 minutes
E7
Not available
O
00
Not available
Use at 00 conditions
–
01
E8
Fan operation control at
heating Thermo - OFF
O
00
Not activated function
This function reduces the unit fan
speed to prevent cold draughts.
01
Activated function
E9
Not available
O
00
Not available
Use at 00 conditions
–
01