6.3.2 List of optional remote control functions
Part
Optional function
Indivi
dual
settin
g
Settings
Condition
setting
Description
B1
Elimination of the heating
temperature offset
O
00
Standard
setting.
Selected
temperature
+4 °C increase
This function is used when the
temperature setting displayed on the
remote control and the inlet air
temperature of the indoor unit are to be the
same.
01
Offset
elimination
02
Selected
tempe4
°C increase
1
b2
Forced air circulation
function on reaching the
set temperature
O
00
Not available
This function prevents air stratification in
the room after stopping the air conditioning
system.
01
Available
b3
Forced compressor
operation for at least three
minutes
O
00
Not available
This function is used to protect the
compressor, preventing it from being
started or stopped for periods of less than
three minutes.
01
Available
b4
Pre-determined filter
cleaning period change
O
00
Standard
This function is used to modify the period
during which the remote control indicates
that the air filter must be replaced.
01
100 hours
02
1200 hours
03
2500 hours
04
Not indicated
b5
Operation mode interlock
X
00
Not available
Once the unit operating mode has been
selected, this function prevents it from
being modified from the remote control.
01
Available
b6
Set temperature interlock
X
00
Not available
Once the temperature on the unit has been
selected, this function prevents it from
being modified from the remote control.
01
Available
b7
Cooling operation interlock
X
00
Not available
This function is available to use
refrigeration mode only and to prevent
heating mode from being enabled.
01
Available
b8
Automatic cooling/ heating
operation
X
00
Not available
This function allows for cooling mode to be
changed automatically to heating mode
(for all units of the same refrigerant cycle).
01
Available
b9
Fan speed interlock
X
00
Not available
Once the fan speed on the unit has been
selected, this function prevents it from
being modified from the remote control.
01
Available
bA
Not used
X
- -
permane
nt
Not used
–
6 Optional functions
198
SMGB0063 rev. 1 - 10/2010
Содержание Econofresh
Страница 2: ......
Страница 4: ...Index ii SMGB0063 rev 1 10 2010 ...
Страница 12: ...Index x SMGB0063 rev 1 10 2010 ...
Страница 24: ...1 General information 12 SMGB0063 rev 1 10 2010 ...
Страница 77: ...Example of installation Example of installation 2 Unit installation 65 SMGB0063 rev 1 10 2010 2 ...
Страница 88: ...2 Unit installation 76 SMGB0063 rev 1 10 2010 ...
Страница 155: ... Wiring diagrams for the RCIM 1 0 2 0 FSN2 indoor units 4 Electrical wiring 143 SMGB0063 rev 1 10 2010 4 ...
Страница 156: ... Wiring diagrams for the RCD 1 0 5 0 FSN2 indoor units 4 Electrical wiring 144 SMGB0063 rev 1 10 2010 ...
Страница 157: ... Wiring diagrams for the RPC 2 0 6 0 FSN2E indoor units 4 Electrical wiring 145 SMGB0063 rev 1 10 2010 4 ...
Страница 158: ... Wiring diagrams for the RPI 0 8 1 5 FSN2E indoor units 4 Electrical wiring 146 SMGB0063 rev 1 10 2010 ...
Страница 159: ... Wiring diagrams for the RPI 2 0 6 0 FSN2E indoor units 4 Electrical wiring 147 SMGB0063 rev 1 10 2010 4 ...
Страница 160: ... Wiring diagrams for the RPI 8 0 10 0 FSN2E indoor units 4 Electrical wiring 148 SMGB0063 rev 1 10 2010 ...
Страница 161: ... Wiring diagrams for the RPIM 0 8 1 5 FSN2E DU indoor units 4 Electrical wiring 149 SMGB0063 rev 1 10 2010 4 ...
Страница 162: ... Wiring diagrams for the RPK 1 0 1 5 FSN2M indoor units 4 Electrical wiring 150 SMGB0063 rev 1 10 2010 ...
Страница 163: ... Wiring diagrams for the RPK 1 0 1 5 FSNH2M indoor units 4 Electrical wiring 151 SMGB0063 rev 1 10 2010 4 ...
Страница 164: ... Wiring diagram for the RPK 2 0FSN2M indoor unit 4 Electrical wiring 152 SMGB0063 rev 1 10 2010 ...
Страница 165: ... Wiring diagrams for the RPK 2 5 4 0 FSN2M indoor units 4 Electrical wiring 153 SMGB0063 rev 1 10 2010 4 ...
Страница 166: ... Wiring diagrams for the RPF I 1 0 2 5 FSN2E indoor units 4 Electrical wiring 154 SMGB0063 rev 1 10 2010 ...
Страница 168: ... KPI 1002 2002 E H 2E energy heat recovery unit 4 Electrical wiring 156 SMGB0063 rev 1 10 2010 ...
Страница 169: ... KPI 3002H2E heat recovery unit 4 Electrical wiring 157 SMGB0063 rev 1 10 2010 4 ...
Страница 170: ...4 Electrical wiring 158 SMGB0063 rev 1 10 2010 ...
Страница 190: ...5 3 3 Activation of the control with protection device 5 Control system 178 SMGB0063 rev 1 10 2010 ...
Страница 192: ...5 Control system 180 SMGB0063 rev 1 10 2010 ...
Страница 234: ...6 Optional functions 222 SMGB0063 rev 1 10 2010 ...
Страница 252: ...9 1 RCD 1 0 3 0 FSN2 9 Spare parts 240 SMGB0063 rev 1 10 2010 ...
Страница 254: ...9 2 RCD 4 0 5 0 FSN2 9 Spare parts 242 SMGB0063 rev 1 10 2010 ...
Страница 256: ...9 3 RPC 4 0 6 0 FSN2E 9 Spare parts 244 SMGB0063 rev 1 10 2010 ...
Страница 258: ...9 4 RPI 0 8 1 5 FSNE 9 Spare parts 246 SMGB0063 rev 1 10 2010 ...
Страница 260: ...9 5 RPI 8 0 10 0 FSN2E 9 Spare parts 248 SMGB0063 rev 1 10 2010 ...
Страница 262: ...9 6 RPIM 0 8 1 5 FSNE DU 9 Spare parts 250 SMGB0063 rev 1 10 2010 ...
Страница 264: ...9 7 RPK 1 0 1 5 FSN2E 9 Spare parts 252 SMGB0063 rev 1 10 2010 ...
Страница 268: ...9 9 RPK 2 0 FSN2E 9 Spare parts 256 SMGB0063 rev 1 10 2010 ...
Страница 270: ...9 10 RPK 2 5 4 0 FSN2E 9 Spare parts 258 SMGB0063 rev 1 10 2010 ...
Страница 272: ...9 11 RPF 1 0 2 5 FSN2E 9 Spare parts 260 SMGB0063 rev 1 10 2010 ...
Страница 274: ...9 12 RPFI 1 0 2 5 FSN2E 9 Spare parts 262 SMGB0063 rev 1 10 2010 ...
Страница 276: ...9 Spare parts 264 SMGB0063 rev 1 10 2010 ...
Страница 314: ...Nº Part 1 Air filter 2 Screws 3 Air filter fixture bar 10 Servicing 302 SMGB0063 rev 1 10 2010 ...
Страница 407: ......