Type of main switch
Select the main switch according to the following table:
Model
Power
supply
Max. current (A)
Circuit breaker
(A)
Earth
leakage breaker (no. of
poles/A/mA)
All indoor units
(*)
1 alternating phase,
230 V, 50 Hz
5
6
2/40/30
KPI-(502/802)E2E
4
6
KPI-(1002)E2E
8
10
KPI-(1502/2002)E2E
8
16
KPI-(3002)H2E
12
16
(*)
Except RPI-(8.0/10.0)FSN2E
4.1.2 Electrical connection of RCI units
Work prior to the electrical connection
1
Turn off the power supply switches before starting work and fit the appropriate locks and safety warnings.
2
Wait 5 minutes after turning off the power supply switches.
3
Check that the fans on the indoor and outdoor units are at a standstill before starting work.
N O T E
•
The electrical power for the unit must involve a specific power line, with an exclusive power control switch and
residual current breaker, installed in line with local or national safety regulations.
•
Check that the electrical power line has enough capacity to supply the unit. Its length, the cable diameter and
their protection (sleeve or jacket) must be appropriate for the unit.
•
For further information, always consider the current regulations in the country where the unit is to be installed.
C A U T I O N
•
Risk of fire: cables must never touch the gas refrigerant pipes, printed circuit boards (PCB), sharp edges or
electrical components inside the unit to avoid damaging them.
•
Loose connection terminals may lead to cable and terminal overheating. The unit may operate incorrectly,
leading to a risk of fire. Check that the cables are firmly secured to the connection terminals.
Electrical connection
Check that the power supply for the RCI indoor unit is 230 V. If not, replace the CN connectors on the TF transformers in
the electrical box.
Make the connection between the indoor unit and the air panel.
N O T E
•
To prevent the screws from falling from the terminal strip, do not remove them completely, hold onto the
terminal and check that the screw is secure through the hole.
•
Use the following screws for the terminal strip:
– M4 screw for the power supply.
– M3.5 screw for the communication line.
4 Electrical wiring
113
SMGB0063 rev. 1 - 10/2010
4
Содержание Econofresh
Страница 2: ......
Страница 4: ...Index ii SMGB0063 rev 1 10 2010 ...
Страница 12: ...Index x SMGB0063 rev 1 10 2010 ...
Страница 24: ...1 General information 12 SMGB0063 rev 1 10 2010 ...
Страница 77: ...Example of installation Example of installation 2 Unit installation 65 SMGB0063 rev 1 10 2010 2 ...
Страница 88: ...2 Unit installation 76 SMGB0063 rev 1 10 2010 ...
Страница 155: ... Wiring diagrams for the RCIM 1 0 2 0 FSN2 indoor units 4 Electrical wiring 143 SMGB0063 rev 1 10 2010 4 ...
Страница 156: ... Wiring diagrams for the RCD 1 0 5 0 FSN2 indoor units 4 Electrical wiring 144 SMGB0063 rev 1 10 2010 ...
Страница 157: ... Wiring diagrams for the RPC 2 0 6 0 FSN2E indoor units 4 Electrical wiring 145 SMGB0063 rev 1 10 2010 4 ...
Страница 158: ... Wiring diagrams for the RPI 0 8 1 5 FSN2E indoor units 4 Electrical wiring 146 SMGB0063 rev 1 10 2010 ...
Страница 159: ... Wiring diagrams for the RPI 2 0 6 0 FSN2E indoor units 4 Electrical wiring 147 SMGB0063 rev 1 10 2010 4 ...
Страница 160: ... Wiring diagrams for the RPI 8 0 10 0 FSN2E indoor units 4 Electrical wiring 148 SMGB0063 rev 1 10 2010 ...
Страница 161: ... Wiring diagrams for the RPIM 0 8 1 5 FSN2E DU indoor units 4 Electrical wiring 149 SMGB0063 rev 1 10 2010 4 ...
Страница 162: ... Wiring diagrams for the RPK 1 0 1 5 FSN2M indoor units 4 Electrical wiring 150 SMGB0063 rev 1 10 2010 ...
Страница 163: ... Wiring diagrams for the RPK 1 0 1 5 FSNH2M indoor units 4 Electrical wiring 151 SMGB0063 rev 1 10 2010 4 ...
Страница 164: ... Wiring diagram for the RPK 2 0FSN2M indoor unit 4 Electrical wiring 152 SMGB0063 rev 1 10 2010 ...
Страница 165: ... Wiring diagrams for the RPK 2 5 4 0 FSN2M indoor units 4 Electrical wiring 153 SMGB0063 rev 1 10 2010 4 ...
Страница 166: ... Wiring diagrams for the RPF I 1 0 2 5 FSN2E indoor units 4 Electrical wiring 154 SMGB0063 rev 1 10 2010 ...
Страница 168: ... KPI 1002 2002 E H 2E energy heat recovery unit 4 Electrical wiring 156 SMGB0063 rev 1 10 2010 ...
Страница 169: ... KPI 3002H2E heat recovery unit 4 Electrical wiring 157 SMGB0063 rev 1 10 2010 4 ...
Страница 170: ...4 Electrical wiring 158 SMGB0063 rev 1 10 2010 ...
Страница 190: ...5 3 3 Activation of the control with protection device 5 Control system 178 SMGB0063 rev 1 10 2010 ...
Страница 192: ...5 Control system 180 SMGB0063 rev 1 10 2010 ...
Страница 234: ...6 Optional functions 222 SMGB0063 rev 1 10 2010 ...
Страница 252: ...9 1 RCD 1 0 3 0 FSN2 9 Spare parts 240 SMGB0063 rev 1 10 2010 ...
Страница 254: ...9 2 RCD 4 0 5 0 FSN2 9 Spare parts 242 SMGB0063 rev 1 10 2010 ...
Страница 256: ...9 3 RPC 4 0 6 0 FSN2E 9 Spare parts 244 SMGB0063 rev 1 10 2010 ...
Страница 258: ...9 4 RPI 0 8 1 5 FSNE 9 Spare parts 246 SMGB0063 rev 1 10 2010 ...
Страница 260: ...9 5 RPI 8 0 10 0 FSN2E 9 Spare parts 248 SMGB0063 rev 1 10 2010 ...
Страница 262: ...9 6 RPIM 0 8 1 5 FSNE DU 9 Spare parts 250 SMGB0063 rev 1 10 2010 ...
Страница 264: ...9 7 RPK 1 0 1 5 FSN2E 9 Spare parts 252 SMGB0063 rev 1 10 2010 ...
Страница 268: ...9 9 RPK 2 0 FSN2E 9 Spare parts 256 SMGB0063 rev 1 10 2010 ...
Страница 270: ...9 10 RPK 2 5 4 0 FSN2E 9 Spare parts 258 SMGB0063 rev 1 10 2010 ...
Страница 272: ...9 11 RPF 1 0 2 5 FSN2E 9 Spare parts 260 SMGB0063 rev 1 10 2010 ...
Страница 274: ...9 12 RPFI 1 0 2 5 FSN2E 9 Spare parts 262 SMGB0063 rev 1 10 2010 ...
Страница 276: ...9 Spare parts 264 SMGB0063 rev 1 10 2010 ...
Страница 314: ...Nº Part 1 Air filter 2 Screws 3 Air filter fixture bar 10 Servicing 302 SMGB0063 rev 1 10 2010 ...
Страница 407: ......