4. Capacity and selection data
TCGB0075 rev.0 - 11/2012
69
4
Mono-valent system
The YUTAKI S80 is sized to provide 100% of the heating requirements on the coldest day of the year.
Example of Mono-valent system
N O T E
•
T
A
: Outdoor ambient temperature.
•
P
H
: Heating capacity.
Air to water heat
pump Capacity
Heat Demand
Air to water heat pump
Design point
P
H
T
A
Mono-energy system
The YUTAKI S80 is sized to provide approximately 80% of the heating requirements in the coldest days of the year. An
auxiliary electric heater (as accessory) is used to provide the additional heating required on cold days.
Example of Mono-energy system
N O T E
•
T
A
: Outdoor ambient temperature.
•
P
H
: Heating capacity.
• SP1/2/3: Heater steps.
•
Bivalent point can be set through the LCD
user’s interface.
Air to water heat
pump + EH capacity
Air to water heat
pump capacity
Heat demand
Air to water heat pump
Air to water
heat pump +
Heater
Bi-valent point
P
H
T
A
Alternating Bi-valent system
The boiler is configured to alternate with the split air to water heat pump. A hydraulic separator of buffer tank has to be used
to ensure hydraulic balancing.
Example of Alternating Bi-valent system
N O T E
•
T
A
: Outdoor ambient temperature.
•
P
H
: Heating capacity.
•
Bivalent point can be set through the LCD
user’s interface.
Air to water heat
pump Capacity
Heat Demand
Air to water heat pump
Boiler
Bi-valent point
P
H
T
A
Содержание 7E300020
Страница 2: ......
Страница 4: ......
Страница 18: ......
Страница 54: ......
Страница 83: ...6 Working range TCGB0075 rev 0 11 2012 83 6 6 Working range Index 6 1 Working range 84 ...
Страница 94: ......
Страница 134: ......
Страница 146: ......
Страница 150: ......
Страница 156: ......
Страница 157: ......