9. Refrigerant and water piping
TCGB0075 rev.0 - 11/2012
112
9.3.3 Water quality
C A U T I O N
• Water quality must be according to EU council directive 98/83 EC.
• Water should be subjected to filtration or to a softening treatment with chemicals before application as treated
water.
•
It is also necessary to analyse the quality of water by checking pH, electrical conductivity, ammonia ion con-
tent, sulphur content, and others. Should the results of the analysis be not good, the use of industrial water
would be recommended for the heating coil circuit.
• It is mandatory to do not add any kind of antifreeze product to the water circuit.
•
To avoid deposits of scale on the heating coil surface it is mandatory to ensure a high water quality with low
levels of CaCO
3
.
The following is the recommended standard water quality.
Item
DHW space
Tendency
(1)
Water supplied
(3)
Corrosion
Deposits of
scales
Electrical Conductivity (mS/m) (25°C)
{µS/cm} (25 °C)
(2)
100~2000
Chlorine Ion (mg CI¯/I)
max. 250
Sulphate (mg/l)
max. 250
Combination of chloride and sulphate (mg/l)
max. 300
Total Hardness (mg CaCO
3
/I)
60~150
N O T E
•
(1): The mark “ ” in the table means the factor concerned with the tendency of corrosion or deposits of scales.
•
(2): The value showed in “
{}
” are for reference only according to the former unit.
• (3): Water range will be according s/UNE 112076:2004 IN.
Содержание 7E300020
Страница 2: ......
Страница 4: ......
Страница 18: ......
Страница 54: ......
Страница 83: ...6 Working range TCGB0075 rev 0 11 2012 83 6 6 Working range Index 6 1 Working range 84 ...
Страница 94: ......
Страница 134: ......
Страница 146: ......
Страница 150: ......
Страница 156: ......
Страница 157: ......