Humidity:
■
Operational: 20-80%
■
Storage: 10-90%
■
Transit: 5-95%
Noise: A-weighted Sound Power Level, Lwa (db re 1pW):
■
Typical: 71
■
Max: 81
Shock and vibration:
■
Optional random vibration: 10 to 350 Hz @ 0.18 Grms
■
Non-operational sinusoidal vibration: 60 to 350 Hz: @ 1g
■
Non-operational shock: 3g 11ms, half sine
Packaged transport
specification:
■
Drops from 356mm and 508mm as per ASTM D5276
■
Vibration at up to 0.53 Grms as per ASTM D4728
Altitude:
■
Maximum of 2000 meters
Ventilation
There are vents and fan openings on the front and the rear of the server. These openings
are designed to allow
airflow,
which prevents the server from overheating.
Note:
At least four inches of clearance must be present at the rear of the
server rack so that
airflow
is unrestricted.
Caution:
Do not place the server in a built-in installation unless proper ventilation is
provided.
Do not operate the server in a cabinet whose internal ambient temperature
exceeds 35º C (95º F).
Server front panel
The front of these servers feature a removable bezel that shields the front-facing server
components.
Ventilation
Chapter 4: Hitachi NAS Platform server components
Hitachi NAS Platform and Hitachi
Unified
Storage Series 4000 Hardware Reference