- 38 -
4.5 Wire Controller All Prohibition Setting
Taking the Mapping Table communication address of the first indoor unit as example, operate 40084 address, refer to the
Mapping Table for others, as follows:
Modbus RTU:
Wire controller all prohibited: 32 10 9C 94 00 01 02 00 01 67 BC
Wire controller clear all prohibited: 32 10 9C 94 00 01 02 00 02 27 BD
Modbus TCP:
Wire controller all prohibited: 00 01 00 00 00 09 FF 10 9C 94 00 01 02 00 01
Wire controller clear all prohibited: 00 01 00 00 00 09 FF 10 9C 94 00 01 02 00 02
4.6 Wire Controller Partial Prohibition Setting
Note
●
After sent one control command, need to wait for the correct response code returned by Modbus before sending next
control command. If do not take this as your control method, please set the internal between two control command to
be more than 500ms.
●
When using this function, note that wire controller must be installed.
●
For one wire controller with multiple indoor units, wire controller prohibition function can only be set on the host
rather than the slave machine, if it’s set, there may be problems (in the same system, the address of main indoor unit
is the smallest one, others are slave indoor units).
Wire controller prohibition includes: all prohibition and partial prohibition.
Wire controller switch on/off prohibition, taking the Mapping Table communication address of the first indoor unit as example,
operate 40085 address, and refer to the Mapping Table for others, as follows:
Modbus RTU:
Wire controller switch on/off prohibited: 32 10 9C 95 00 01 02 00 01 66 6D
Wire controller switch on/off clear prohibited: 32 10 9C 95 00 01 02 00 00 A7 AD
Modbus TCP:
Wire controller switch on/off prohibited: 00 01 00 00 00 09 FF 10 9C 95 00 01 02 00 01
Wire controller switch on/off clear prohibited: 00 01 00 00 00 09 FF 10 9C 95 00 01 02 00 00
Wire controller operating mode prohibition, taking the Mapping Table communication address of the first indoor unit as example,
operate 40086 address, refer to the Mapping Table for others, as follows:
Modbus RTU:
Wire controller operating mode prohibited: 32 10 9C 96 00 01 02 00 01 66 5E
Wire controller operating mode clear prohibited: 32 10 9C 96 00 01 02 00 00 A7 9E
Modbus TCP:
Wire controller operating mode prohibited: 00 01 00 00 00 09 FF 10 9C 96 00 01 02 00 01
Wire controller operating mode clear prohibited: 00 01 00 00 00 09 FF 10 9C 96 00 01 02 00 00