Apply by making
contact to the piping.
Check that there are no gaps between the
Switch Box and the insulation.
Apply by making
contact to the piping.
Check that there are no gaps
between the Switch Box and the
insulation.
Check that there are no gaps between
the Switch B
ox
and the insulation.
Check there are no gaps between insulation materials.
If the gaps are occurs, seal the gap with vinyl tape.
Securely fasten.
Securely fasten cable clamps
and the vinyl tape.
Securely fasten cable clamps
and the vinyl tape.
Insulation
(Field-Supplied)
Insulation
(Field-Supplied)
Insulation
(Field-Supplied)
Insulation
(Accessory (6))
Insulation
(Accessory (5))
Clamp
(Accessory (7))
Securely fasten.
Clamp
(Accessory (7))
Insulation Material
(Attached to the Switch Box)
Insulation Material
(Attached to the Switch Box)
Insulation Material
(Attached to the Switch Box)
Insulation Material
(Attached to the Switch Box)
Insulation Material
(Attached to the Switch Box)
Switch Box Side
Switch Box Side
Insulation
(Field-Supplied)
Insulation
(Field-Supplied)
Insulation
(Field-Supplied)
Insulation Work for Gas (High/Low Pressure and Low Pressure)
Pipe of Outdoor Unit Side
Insulation Work for Liquid Pipe of Outdoor Unit Side
Insulation Work for Gas Pipe of Indoor Unit Side
Insulation Work for Liquid Pipe of Indoor Unit Side
Switch Box Side
Switch Box Side
(d) In
case
there
are
unused
piping
connection,
ensure
to
apply
accessory
insulation
material
to
the
piping
and
flar
e
connections
without
gaps
as
shown
on
the
right
figure
(For
gas
and
liquid
sides)
Insulate without gaps.
Insulation
(Accessory (5), (6))
Securely fasten.
Clamp
(Accessory (7))
(b) Insulate
gas
and
liquid
pipe
separately
using
the
accessory
insulation
material.
In
the
event
that
temperature
and
humidity
levels
inside
the
ceiling
exceed
30
°
C
(86
o
F)/RH,
relative
humidity
80%,
apply
additional
insulation
materials
(approximately
10mm
(3/8
inch)
thickness)
to
the
surface
of
the
accessory
insulation
material
to
avoid
condensation.
(c)
Perform
cold
insulation
work
by
insulating
and
taping
the
flar
e
connection
and
reducer
connection.
Also
insulate
all
the
refrigerant
pipes.
20