(3) Selecting
Piping
Size
●
●
Select the size for the high/low pressure gas pipe,
low pressure gas pipe and liquid pipe according
to
T
able 5.1. The size depends on the indoor unit
total capacity connected downstream of the
Switch Box.
As for the
BRANCH PIPE
branch or header branch,
refer
to the
T
echnical Catalog for the Outdoor Unit.
●
Perform the piping connection work for the
Switch
Box
as shown below.
(a) Outdoor
Unit
Side
Field
Piping
Size
Table
5.1
Outdoor
Unit
Side
Field
Piping
Size
Connected
Indoor
Unit
Capacity:
Q
Low
Pressure
Gas
Pipe
(A)
High/Low
Pressure
Gas
Pipe
(B)
Liquid
Pipe
(C)
kW
mm (inch)
mm (inch)
mm (inch)
<
16.0
f
15.88 (5/8)
f
12.7 (1/2)
f
9.52 (3/8)
16.0
≤
Q
<
25.0
f
19.05 (3/4)
f
15.88 (5/8)
f
9.52 (3/8)
25.0
≤
Q
<
33.5
f
22.2 (7/8)
f
19.05 (3/4)
f
9.52 (3/8)
33.5
≤
Q
<
45.0
f
25.4 (1)
f
22.2 (7/8)
f
12.7 (1/2)
45.0
≤
Q
<
50.0
f
28.58 (1-1/8)
f
22.2 (7/8)
f
12.7 (1/2)
50.0
≤
Q
<
61.5
f
28.58 (1-1/8)
f
22.2 (7/8)
f
15.88 (5/8)
61.5
≤
Q
<
73.0
f
28.58 (1-1/8)
f
25.4 (1)
f
15.88 (5/8)
73.0
≤
Q
≤
85.0
f
31.75 (1-1/4)
f
28.58 (1-1/8)
f
19.05 (3/4)
NOTE:
Refer to “Position of Piping Connection” for the details of the piping connection for the
Switch Box
.
Use field-supplied reducer in case the field piping and
Switch Box
piping
connection does not match.
(a) Outdoor Unit Connecting Side
High/Low Pressure
Gas Pipe (B)
(Field-Supplied)
(Field-Supplied)
(Field-Supplied)
(Field-Supplied)
(Field-Supplied)
Low Pressure
Gas Pipe (A)
Liquid Pipe (C)
Gas Pipe (D)
Liquid Pipe (E)
(b) Indoor Unit Connecting Side
15