background image

 

Installation PTN-2-C37.94 with E1/PTN-2-C37.94 with T1 

Release 01 02/2018 

 

Figure 1

 

Common Example with C37.94, E1, T1 

 

1.2

 

Manual References 

Table 1 is an overview of the manuals referred to in this manual. ‘&’ refers to the language 
code,  ‘*’  refers  to  the  manual  issue.  All  these  manuals  can  be  found  in  the  HiProvision 
(=Dragon PTN Management System) Help function. 

Table 1

 

Manual References 

Ref. 

Number 

Title 

[1] 

DRA-DRM821-&-* 

Dragon PTN and HiProvision Operation 

[2] 

DRA-DRM801-&-* 

Dragon PTN Installation and Operation 

[3] 

DRB-DRM802-&-* 

Dragon PTN Nodes: PTN2210, PTN2209, PTN2206, PTN1104 

[4] 

DRD-DRM803-&-* 

Dragon PTN Switching Module: PTN-CSM310-A 

[5] 

DRE-DRM805-&-* 

Dragon PTN Interface Module: PTN-4-E1-L/PTN-4-T1-L 

[6] 

DRF-DRM811-&-* 

Dragon PTN TRMs (Transmit Receive Modules: SFP, XFP) 

[7] 

DRA-DRM810-&-* 

Dragon PTN General Specifications 

[8] 

DRE-DRM818-&-* 

Dragon PTN Switching Module: PTN-16-E1-L/PTN-16-T1-L 

 

MPLS-TP Dragon PTN Network

WAN (via SFP on fiber)

2-C37.94

Module

Dragon PTN 

Node

Packetized C37.94/E1/T1 via

SAToP and CESoPSN

LAN1

codec

PBX

Teleprotection1

LAN2

codec

PBX

Teleprotection2

C37.94

Fiber Links

E1/T1 

Links

C37.94

Fiber Links

E1/T1 

Links

Содержание PTN-2-C37.94

Страница 1: ...n PTN 2 C37 94 with E1 PTN 2 C37 94 with T1 Technical support Release 01 02 2018 https hirschmann support belden com User Manual Installation Dragon PTN Interface Module PTN 2 C37 94 with E1 PTN 2 C37...

Страница 2: ...r own use The performance features described here are binding only if they have been expressly agreed when the contract was made This document was produced by Hirschmann Automation and Control GmbH ac...

Страница 3: ...9 SAToP Compared With CESoPSN 19 2 2 10 Hitless Switching 19 2 2 11 Single Path 20 2 2 12 Delay Comparison in CES Features 22 2 2 13 I O with the Central Switching Module CSM 22 2 2 14 Synchronizatio...

Страница 4: ...1 SAToP Example 14 Figure 13 General CESoPSN via C37 94 Port Example 15 Figure 14 Detailed C37 94 to C37 94 CESoPSN Example 16 Figure 15 General CESoPSN via E1 T1 Port Example 16 Figure 16 Detailed E1...

Страница 5: ...D Indications In Normal Operation 9 Table 4 E1 T1 RJ 45 Connector Pin Assignments 10 Table 5 Comparison SAToP CESoPSN 19 Table 6 Difference Between Hitless and Protection Switching 20 Table 7 Clocking...

Страница 6: ...t power system A C37 94 frame also has a bandwidth of 2 048 Mbps and all its information is also transported in 32 timeslots just like E1 But C37 94 is a special kind of E1 framing Within these 32 E1...

Страница 7: ...A DRM801 Dragon PTN Installation and Operation 3 DRB DRM802 Dragon PTN Nodes PTN2210 PTN2209 PTN2206 PTN1104 4 DRD DRM803 Dragon PTN Switching Module PTN CSM310 A 5 DRE DRM805 Dragon PTN Interface Mod...

Страница 8: ...the Node Untighten the two fastening screws in the front panel corners Take the front panel handles to pull out and finally remove the module from the Dragon PTN node 2 1 2 LEDs The meaning of the LE...

Страница 9: ...port no alarms detected on backplane network side everything fine Orange lit service on this port no network traffic or RDI detected on backplane network side Orange blinking other errors different fr...

Страница 10: ...see 2 3 2b The cables below can be ordered to connect these ports E1 cable 120 ordering number 942 256 201 T1 cable 100 ordering number 942 256 200 Figure 4 E1 T1 RJ 45 Connector Table 4 E1 T1 RJ 45...

Страница 11: ...2 7 for some examples Figure 5 Detailed Function C37 94 E1 T1 Example 2 2 2 E1 Framing E1 is a 2 048 Mbps bi directional full duplex link through which the data is transported in a digital way in fra...

Страница 12: ...the Least Significant Bit of the time slots in each multiframe agreed upon in band NOTE Multiframe E SF Extended Super Frame future support Frame 125 s 24 time slots Bit slot Time slot 0 F Frame 1 1 1...

Страница 13: ...ssive zeros E1 HDB3 replace four successive zeros with a fixed bit pattern 000V or B00V T1 B8ZS replace eight successive zeros with a fixed bit pattern 000VB0VB A B and V can either be or Which patter...

Страница 14: ...per port Figure 11 General SAToP Example In the figure below a more detailed E1 frame example has been worked out Figure 12 Detailed E1 SAToP Example ALL channels MPLS TP Dragon PTN C37 94 E1 T1 port...

Страница 15: ...tween two or more E1 ports see below Between two or more T1 ports see below Between a C37 94 and an E1 port see below Between a C37 94 and a T1 port see below a Between Two C37 94 Ports One CES per C3...

Страница 16: ...first selected source timeslot will be mapped automatically onto the first selected destination timeslot etc See some examples in the figures below NOTE In E1 timeslot 0 cannot be transported Figure...

Страница 17: ...mple if the configured amount is five then timeslot 1 2 3 4 5 will be transported The remaining timeslots on the C37 94 port cannot be used anymore On the destination side or E1 port the transported t...

Страница 18: ...To E1 CESoPSN Example e Between a C37 94 and a T1 Port Similar to 2 2 7d MPLS TP Dragon PTN Unused ALL channels Site A Site B Site C Site A CESoPSN 1 C37 94 port C37 94 frame E1 port Site B Site C Unu...

Страница 19: ...output side Between C37 94 and E1 port timeslot x on the input side can be mapped to timeslot y on the output side Per CESoPSN service the timeslots on the input side must be part of the same port the...

Страница 20: ...ding on the enabled sub features see also further on Table 6 Difference Between Hitless and Protection Switching C37 94 E1 T1 Protection Switching C37 94 E1 T1 Hitless Switching required tunnel type 1...

Страница 21: ...packet loss when the fastest path comes up later on See 2 2 12 for a delay comparison within CES depending on the enabled sub features see also further on Figure 20 Single Path Enabled Figure 21 Singl...

Страница 22: ...der 2 2 14 Synchronization Clock Distribution Network Timing CAUTION Make sure to configure verify the clocking parameters below The Dragon PTN network provides a number of mechanisms to perform synch...

Страница 23: ...lock Master Dragon PTN A B D C Internal Rx Adaptive Rx Dragon PTN A B D C Internal Rx Differential Rx SyncE PRC Clock Master Clock Slave E1 T1 C3794 CODIR 7 Serial synchronous E1 T1 C3794 CODIR SyncE...

Страница 24: ...its clock to this stream Both Applications A and D slave to Dragon PTN Clock Master Rx Clock Internal Clock Unchecked Adaptive Differential Rx Clock Node B transmits packets to node C based on an Inte...

Страница 25: ...ervice creation NOTE This setting is not relevant for the C37 94 ports 2 2 16 Test and Loopback Selftests Test and Loopback selftests can be performed in CESes e g when configuring or troubleshooting...

Страница 26: ...ated in Figure 24 and Figure 26 and must not be changed This switch is only relevant for the E1 T1 ports The configuration can be read out via HiProvision For more information on E1 T1 framing see 2 2...

Страница 27: ...rmation on the network resulting in a lot of consumed bandwidth Encoding more frames into one packet will decrease the amount of header information and as a result the consumed bandwidth as well As of...

Страница 28: ...t this value to Packetizing Delay expected peak to peak jitter s the default peak to peak jitter could be 250 s the expected peak to peak jitter s must be measured in the network If the packetizing de...

Страница 29: ...axNetwPathDelayDiff 1087 Total P Path Delay DP DPh 3 3 4 Estimated Delay Examples Find some example values below Fill them out in the formulas to find the estimated total delay TDMFramesPerPacket 10 P...

Страница 30: ...application or network Based on these findings bandwidth and delay parameters can be tuned Some examples according the information in 3 2 and 3 3 if bandwidth is not a problem and a small delay is wan...

Страница 31: ...t 126 mm 4 96 inches depth 195 mm 7 68 inches Power Consumption 27W measured at 25 C 77 F with data transport 5 3 Ordering Information PTN 2 C37 94 942 236 009 6 ABBREVIATIONS AIS Alarm Indication Sig...

Страница 32: ...Most Significant Bit MTBF Mean Time Between Failures NTR Network Timing Reference OAM Operations Administration and Maintenance PBX Private Branch Exchange PF Power Failure PI Power Input PTN Packet T...