10
Installation BAT-R
Release 09 03/2017
the housing is closed
the terminal blocks are wired correctly
the terminal blocks for the power supply are connected
For supply voltage connections with protective conductor connection:
First connect the protective conductor before connecting the wires for
the supply voltage.
If your device comprises a 2nd supply voltage connection of this type:
First connect the protective conductor before connecting the wires for
the supply voltages.
ATEX directive 2014/34/EU – specific regulations for safe
operation
In Ex zone 2, only devices with a corresponding label may be operated.
When operating the BAT-R types with characteristic value G for
approvals 1 (ATEX zone 2), the following applies:
Never use the supply voltage with characteristic value K in Ex zone 2.
II 3 G
Ex nA IIC T4 Gc
DEKRA 13ATEX0027 X
–40 °F ... +158 °F (–40 °C ... +70 °C) for temperature range
characteristic value T and E
+32 °F ... +140 °F (0 °C ... +60 °C) for temperature range
characteristic value S
DO NOT OPEN THE DEVICE WHEN IT IS ELECTRICALLY CHARGED.
THE USB CONNECTOR MUST NOT BE USED WHEN THE DEVICE IS
OPERATED IN EXPLOSIVE HAZARDOUS LOCATIONS.
Temperature code T4
Ambient temperature
−
40 °F ... +158 °F (
−
40 °C ... +70 °C ;
temperature range with characteristic value T and E)
Ambient tempe32 °F ... +140 °F (0 °C ... +60 °C;
temperature range with characteristic value S)
List of standards
EN 60079-0:2012 + A11
EN 60079-15:2010