background image

 

Part 

No. 

4801-5801 

Rev. 

4-2010 

    Page 

18

 of 

24

 

 

 

Super Saver XL Heater Maywick 

  

  

b

 

 

 

Gate

 

 

valve

 

  

Arbitrary Piping System

 

 

d

 

 

 

f

 

 

 

Heaters 

Heaters 

30

   

m

   

 

m

  

Gas meter

 

 

8

   

m

  

tees

 

 

 

11.  Pipe Sizing Guidelines 

11.1  Calculating HVR & ELOP 

1. 

Using a system schematic, label each piping 
section of the system starting at the meter or 
regulator.  A different pipe section starts 
where the gas demand of the system 
changes, usually at a junction. 

2. 

Determine the Heating Value Required 
(HVR) in BTUH (BTU's per hour) for each 
section of pipe. 

HVR = (no. heaters supplied by pipe 
section) X (heat output per heater)
 

 

3. 

Determine the Equivalent Length Of Pipe (ELOP) 
required for sufficient gas service. 

ELOP = (length from meter to most remote heater) 
+ (Minor loss equivalents of the system)

 

IMPORTANT:  Use the ELOP value from this 
equation for size determination of all pipe sections. 

4. 

Use the ELOP value from step 3, and the HVR of 
each pipe section to determine the required pipe size 
for either natural gas (NG) (Table 1) or liquid propane 
(LP) (Table 2) from the table 'Maximum Capacity Of 
Pipe'.

 

 

11.2  Directions For Reading Pipe Size From Tables: 

EXAMPLE:  Four 40,000 BTUH (12 kW) heaters will be installed on the gas pipe line in the 'Arbitrary Piping System' 
diagram below.  NOTE:  Values given in English and Metric equivalent units. 

1.  Determine the HVR value for each pipe section of the system.

 

Pipe Section 

No. Of Heaters 

HVR Calculation 

HVR Value  

  

BTUH 

kW 

BTUH 

kW 

a-b 

4 x 40,000 

4 x 12 

160,000 

48 

b-c 

2 x 40,000 

2 x 12 

80,000 

24 

c-e 

1 x 40,000 

1 x 12 

40,000 

12 

b-d 

1 x 40,000 

1 x 12 

40,000 

12 

b-f 

1 x 40,000 

1 x 12 

40,000 

12 

c-g 

1 x 40,000 

1 x 12 

40,000 

12 

2.  Determine the ELOP.  Length from meter to most remote heater = length from a to e (or g) = 100ft (30m) + 25ft 

(8 m) = 125ft (38 m)  Minor loss equivalents from Table 1 = 1 gate valve x  2ft/valve (1 m/valve) + 3 tees x 11 
ft/tee (4 m/tee) =35ft (13 m).  Calculated ELOP = 125ft (38 m) + 35ft (13 m) = 160 ft (51 m)  Tabulated ELOP = 
200ft (60 m)  Round up to the nearest table value. 

3.  In the appropriate table, NG (Table 2) or LP (Table 3), 

select the column showing the ELOP or the next longer 
length, if the table does not give the exact length.  Use 
this column to compare table values to the HVR values.  
Use the Natural Gas table (Table 2) in this example.  
From step 2,  
ELOP = 200ft (60 m)  Locate the column labeled 200ft 
(60 m) in Table 2. 

4. 

Select a pipe section and read down the ELOP column to 
find the maximum gas capacity that matches the HVR for 
that particular pipe section.  If the exact value is not 
listed, choose the next larger value in the column.  In this 
example, start with pipe section c-e.  For pipe section c-
e, HVR = 40,000 BTUH (12 kW). From Table 2, column 
200 ft, 40 (12) is not listed (NOTE: The table values are 
in thousands of BTUH's).  The next larger value of 72 
(21) is read from the table, corresponding to 72,000 
BTUH (21 kW). 

5.  Follow the row leftward until you reach the columns 

labeled 'Internal Diameter' and 'Nominal pipe size'.  Read 
the pipe size for the particular pipe section.  For example, 
for pipe section c-e, the pipe size is ¾ inch (0.824 in.) 
(19.1 mm).  Repeat for each pipe section. 

 

Содержание Maywick SS-225-XL

Страница 1: ...upteurs electriques 3 Etegnex toute flamme hue 4 Contactez immediatement votre compangie de gaz FOR YOUR SAFETY Do not store or use gasoline or any flammable vapors and liquids in the vicinity of this...

Страница 2: ...lvents paint thinner dust particles or unknown chemicals Failure to follow these instructions may result in a fire or explosion property damage personal injury or loss of life WARNING Not for home or...

Страница 3: ...tructions Model No Maximum Input Ventilation air required to support combustion SS 225 XL 225 000 BTUH 65 9 kW 1000 CFM 1699 m3 hr LP Propane Gas Maximum 14 in W C 34 8 mbar and minimum 12 5 in W C 31...

Страница 4: ...be used for heating where flammable liquids and vapors are stored or used 11 Inadequate gas volume and or pressure will directly influence the combustion efficiency of the heater Adequate gas volume a...

Страница 5: ...ect heater and gas connections periodically for gas leaks with an approved gas leak testing solution soap and water work well 6 Keep heater clean at all times A Open doors and blow out dust with high...

Страница 6: ...ions THERE ARE NO WARRANTIES THAT EXTEND BEYOND THE LIMITED WARRANTY DESCRIPTION SET FORTH ABOVE SPECIFICALLY GSI MAKES NO FURTHER WARRANTY OF ANY KIND EXPRESS OR IMPLIED INCLUDING WITHOUT LIMITATION...

Страница 7: ...eveling Adjust cables or chains as required to level the heater Use a carpenter s level to check that the heater is level 5 3 Installing Dual Flare Duct Fold Dual Flare duct to shape as shown in Fig 1...

Страница 8: ...heater will operate every time power is supplied and the on off switch is activated If an external thermostat is to be used See Component Wiring Diagram the heater will operate only when power is sup...

Страница 9: ...rectangle and fasten around exhaust outlet on front of heater with sheet metal screws provided 9 Place heater on support bracket Support bracket must be level before heater is set in place 10 Slide t...

Страница 10: ...oor cover in slots on heater door and slide down This will lock the cover in place on the door See Detail F Repeat this step for the second door 15 To continue with installation of your heater see Use...

Страница 11: ...Part No 4801 5801 Rev 4 2010 Page 11 of 24 Super Saver XL Heater Maywick COMPONENT AND WIRING DIAGRAM 230 Volts A C 50 Hz Single Phase 8 Component and Wiring Diagram...

Страница 12: ...INE VOLTAGE THERMOSTAT 10 AMP FUSE ON OFF TRANSFORMER 24 VAC 40VA 50 60 Hz LINE VOLTAGE LOW LINE UNITED TECHNOLOGIES Hot Surface Ignition Control FLAME SENSOR PROBE GND REDUNDANT VALVE MAIN VALVE HIGH...

Страница 13: ...ed below will help determine if system is operating properly The igniter will warm up and glow bright red The main burner flame will ignite The main burner flame will continue to burn after the ignite...

Страница 14: ...gnition sequence when the false flame is no longer present 4 Status Indicator Flashing Four Times When the status indicator LED shows the repeating error code of four flashes the control has gone into...

Страница 15: ...Part No 4801 5801 Rev 4 2010 Page 15 of 24 Super Saver XL Heater Maywick 10 4 Chart 1 First Visual Check Chart 1 First Visual Check...

Страница 16: ...Part No 4801 5801 Rev 4 2010 Page 16 of 24 Super Saver XL Heater Maywick 10 5 Chart 2 Second Visual Check Chart 2 Second Visual Check NOTE All voltage readings 10 15...

Страница 17: ...Part No 4801 5801 Rev 4 2010 Page 17 of 24 Super Saver XL Heater Maywick 10 6 Chart 3 Third Visual Check Chart 3 Third Visual Check...

Страница 18: ...000 4 x 12 160 000 48 b c 2 2 x 40 000 2 x 12 80 000 24 c e 1 1 x 40 000 1 x 12 40 000 12 b d 1 1 x 40 000 1 x 12 40 000 12 b f 1 1 x 40 000 1 x 12 40 000 12 c g 1 1 x 40 000 1 x 12 40 000 12 2 Determ...

Страница 19: ...500 7200 6700 5500 4600 3783 3432 Table values given in BTUH 1000 To convert to kW multiply table values by 0 3 1 inch 25 4 mm Pipe Sizes Determined For Diagram Pipe Section Max Gas Capacity Value Det...

Страница 20: ...date of manufacture voltage frequency gas type inside or outside mount and whether the heater is constructed of galvanized or stainless steel 1045 1305 Natural Gas 1045 0100 LP Propane Gas 1021 2501 0...

Страница 21: ...Super Saver XL Heater Maywick 3004 6000 3002 5001 24 V 3003 5010 6401 1308 1041 3066 1041 1491 1009 1500 1021 1497 1021 1496 Refer to Model No for Orifice type 0408 4492 1021 1495 1004 1422 6401 0226...

Страница 22: ...Rev 4 2010 Page 22 of 24 Super Saver XL Heater Maywick 0404 4486 6401 2879 6401 1318 0408 1131 3504 4007 3001 1740 3017 3076 240 Volt Heater Plate 3008 2258 3006 1580 1042 2693 3591 0100 1902 1138 30...

Страница 23: ...Part No 4801 5801 Rev 4 2010 Page 23 of 24 Super Saver XL Heater Maywick NOTES...

Страница 24: ...Copyright 2008 by Group Printed in the USA...

Отзывы: