Controller Operation
16
3A6828B
Zeroing the Transducer
Graco-supplied pressure transducers will not be cali-
brated, and will need to be zeroed before running pres-
sure tests. Zeroing a non-calibrated transducer
effectively sets the low pressure setting of the trans-
ducer to 0 PSI within the system.
1. After
Selecting a Transducer
(on page 15), press
the Stop button and perform the
Pressure Relief
Procedure
on page 11.
2. With 0 PSI in the system, press the Zero button on
the Transducer screen.
Calibrating the Transducer
Calibrated pressure transducers do not need to be
zeroed, but their calibration parameters will need to be
entered the Calibration screen.
1. After
Selecting a Transducer
(on page 15), press
the Stop button and perform the
Pressure Relief
Procedure
on page 11.
2. With 0 PSI in the system, press the Calibrate button
on the Transducer screen after
Selecting a Trans-
ducer
to display the Calibration screen.
3. Select the Low Pressure and High Pressure fields,
in turn, and enter the calibration parameters (both
mA and PSI) from the transducer calibration sheet.
NOTE:
The Reset button will reset all fields on the Cali-
bration screen to default values.