Configure
Settings with
Graphical, easy-to-understand
guidance for connection procedures
Quick Setup guides you through the process of setting up the instrument for measurement, right up to starting
measurement, on the screen to simplify set work. Since any mistaken connections will trigger a FAIL message,
the feature also helps prevent measurement mistakes. If you receive a FAIL result, the instrument will also
indicate the location of the problem.
Setup Flow
(example: 3P4W)
Connect the leads to the PW3365-20
Select the current range
Measurement
Connect the voltage sensor
Connect the clamp sensors
Check wire connection status
Quick Set START / Choose the wire type
STEP1
STEP2
STEP3
STEP4
STEP5
STEP6
If you receive a FAIL result
Highlight the FAIL message with the cursor and press ENTER to view
information about where the connection needs to be corrected.
Miswiring Example
(Clamp Orientation)
The I vector’s phase direction is
within the determination area.
Green means : PASS
Red means : FAIL
The I vector’s phase direction is
opposite the determination area.
P: 6.2kW
Power displayed value is too low
P: 17.8kW
Neither power nor power
factor can be measured
accurately with the clamp
in the wrong orientation.
Point the
arrow
toward the
load side
Correct Orientation
Power supply side
Load side
FAIL