Himmelstein MCRT 48200V Скачать руководство пользователя страница 13

13

© 2022 S. Himmelstein and Company—all rights reserved.     www.himmelstein.com

E.3.2 Constant Output Regardless of Shaft 
Torque

If the ¶E.3.1 above Cal Checks are performed and found 
normal, then the problem is the sensor. Return it for 
factory service.

E.3.3 Apparent Zero Drift

•  Check the Cabling. See ¶E.2.2.

•  Check for Driveline Torque Offsets. Torquemeters 

installed in a drive which has hysteresis or friction 
torques, may appear to have long term drift when 
there is none. For example, when installed between 
a pump and a gear drive, the torque reading may not 
return to zero after a test because of locked-in fric-
tion torque. The sensor sees and reads that locked-in 
torque. Always zero the torquemeter with no torque 
on the driveline—in the case cited, with a coupling 
disassembled. At the end of the test, the shaft should 
be mechanically “shaken” or a coupling broken, to 
return to zero torque. Otherwise, the sensor will 
read locked-in torque. A rub between any rotating 
and stationary part is a common cause of friction. 
Verify the shaft couplings and other rotating parts 
have adequate clearance.

E.3.4 Signal Instability

•  Check the Cabling. See ¶E.2.2 above.

•  Check For Driveline Torque Variations. The driveline 

may have a low frequency oscillation which the 
sensor reads (see Tech Memo 8150). Use the Torque-
meters’ low frequency filter to suppress signals 
above 1 Hertz. If the readings become steady, then 
you may wish to identify the physical cause of the 
shaft torque variation or, remove it with mechanical 
filtering techniques. Oscillographic signal analysis 
is often helpful under these conditions. Use the 200 
Hertz filter for this analysis. If very large, high inertia 
machines are used, or large machines are used in a 
control loop, torque and speed oscillations can be 
present below 1 hertz.

E.3.5 System Will Not Zero

•  Check the Cabling. See ¶E.2.2 above.

•  Verify the Torque Input is Zero. If the sensor is 

installed in a driveline, break or remove one of the 
couplings. If the system still can’t be zeroed, then 
the problem is either the cable, system grounding 
or the Torquemeter. Verify cable integrity, configura-
tion and connections and check the Torquemeter per 
¶E.2.1.

•  Verify A Good Earth Ground, per ¶B.2.1, is present.

E.4 Speed Pickup Replacement

Speed pickups are threaded into the sensor stator housing 
and locked with a jam nut.

E.4.1 Removing A Defective Pickup

•  Disconnect the mating cable.

•  With shaft motion stopped

, loosen the jam nut.

•  Back out the defective speed pickup.

E.4.2 Installing A Replacement Pickup

•  With shaft motion stopped

, screw in the new pickup 

until it makes contact with the rotor assembly.

•  Back off the pickup one quarter of a turn.

•  Tighten the jam nut.

•  Slowly rotate the shaft to verify no rub occurs. It you 

detect a rub, re-adjust the pickup.

•  Reconnect the mating cable.

E.4.3 Replacement Part Numbers

•  Standard (Code A) Speed Pickup P/N: 900-1001

•  Zero Velocity (Code Z) Speed Pickup P/N: 900-1007

Содержание MCRT 48200V

Страница 1: ...NON CONTACT DIGITALTORQUEMETER INSTALLATION OPERATION ANDTROUBLESHOOTING GUIDE MCRT 48200V NON CONTACT DIGITALTORQUEMETER INSTALLATION OPERATION ANDTROUBLESHOOTING GUIDE COMPANY 2490 Pembroke Avenue H...

Страница 2: ...te Unless specified differently when ordered default values are as follows Sensor Full Scale 10 Volts Torque Unit of Measure lbf in Filter Cutoff Frequency 10 Hz Password Protection Off These selectio...

Страница 3: ...D 2 3 Starting High Inertias with Electric Motors 10 D 3 Allowable Bearing Loads 11 D 4 Allowable Extraneous Loads 11 D 4 1 Allowable Bending Loads 11 D 4 2 AllowableThrust Loads 11 D 5 Operating Spee...

Страница 4: ...tude variations That data is then transmitted to the stator as infrared IR energy where it is detected and output in industry standard analog and digital formats The IR transmission is inherently tole...

Страница 5: ...force Next allow the assembly to cool to room temperature Then repeat the process for the second coupling If desired use forced air to accelerate cooling Air cooling avoids contaminating the torque m...

Страница 6: ...ailable at www belden com Himmelstein recommends the connec tion in Figure 20 For best results use a differential input amplifier in these electrically noisy environments B 2 2 Power Input 2 Pin Conne...

Страница 7: ...1 Zero Velocity Code Z Pickup Code Z Zero Velocity Speed Pickups have three pin connectors They require external power 6 to 15VDC Connections are as follows Pin A Power In 6 to 15VDC Pin B Output Sig...

Страница 8: ...pe A Pin A Signal Pin B Signal Type Z Pin A POWER IN Pin B Output Signal Pin C Common Notes 1 A dot appears next to Pin 1 on all connectors 2 All cables are shielded 3 Shields Float at Torquemeter end...

Страница 9: ...c data with unit of measure Displays Torque Peak and Valley numeric data with unit of measure Displays Torque Spread numeric data with unit of measure Classifies status of user set High and Low Torque...

Страница 10: ...taneous torque and the torquemeters overload rating as a safety margin for unexpected loads Do not knowingly operate in the overload region If you expect torques in the overload region then change to...

Страница 11: ...inches of bending or 1 of the applied pounds of thrust D 4 1 Allowable Bending Loads When it is applied without thrust a standard MCRT Torquemeter mounted as a floating shaft can handle a shaft bendi...

Страница 12: ...ntial faults The best procedure is to isolate the problem part then correct or replace it Otherwise return the defective part to the factory E 2 Preliminary Inspection E 2 1 Torquemeter Inspect the se...

Страница 13: ...1 Hertz If the readings become steady then you may wish to identify the physical cause of the shaft torque variation or remove it with mechanical filtering techniques Oscillographic signal analysis i...

Страница 14: ...nominal Has reverse polarity and 25 Volt overvoltage protection Available Options Enhanced Performance Code C Code N is standard performance 60 PPR Speed Pickup Options Code A is standard type Code Z...

Страница 15: ...or aType A pickup and 3 pins for aType Z pickup To order spare connectors use the following part numbers P N When the bearing load ratings don t meet the above criteria use pillow blocks and a jack sh...

Страница 16: ...it mantissa with an implied MSB of 1 0x80000000 Sign 0 positive 1 negative 0x7F800000 Exponent 0x007FFFFF Mantissa o if sign 0 then value 2 Exponent 24 Mantissa 0x800000 o else value 2 Exponent 24 Man...

Страница 17: ...se messages can only retrieve information from the MCRT48200V they can not change any data on the MCRT48200V The time returned is the number of 10kHz clock ticks since the MCRT48200V was powered on ME...

Страница 18: ...ut E DAC value to give 10V analog output Miscellaneous Messages MESSAGE REPLY MEANING OK Write data in RAM to non volatile flash PS index string OK Change Flash password protection o string must match...

Страница 19: ...the user Only data from the DC command is subject to this scaling FL int FiLter 0 10 4 bits o 2 200 Hz o 3 100 Hz o 4 50 Hz o 5 20 Hz o 6 10 Hz o 7 5 Hz o 8 2 Hz o 9 1 Hz o 10 0 5 Hz o 11 0 2 Hz o 12...

Страница 20: ...COMPANY 2490 Pembroke Avenue Hoffman Estates IL 60169 847 843 3300 www himmelstein com CDTM...

Отзывы: