5 Programming
HIMax System
HI 801 001 E Rev. 4.01
Page 58 of 122
Variable
Description
Data type
Last IO Warning [s]
01-01
UDINT
Last Communication Warn-
ing [ms]
UDINT
Last Communication Warn-
ing [s]
Date and time of the last communication warning in s and ms
since 1970-01-01
UDINT
Last System Warning [ms]
UDINT
Last System Warning [s]
Date and time of the last system warning in s and ms since
1970-01-01
UDINT
Last IO Error [ms]
UDINT
Last IO Error [s]
Date and time of the last I/O error in s and ms since 1970-01-
01
UDINT
Last Communication Error
[ms]
UDINT
Last Communication Error
[s]
Date and time of the last communication error in s and ms
since 1970-01-01
UDINT
Last System Error [ms]
UDINT
Last System Fault [s]
Date and time of the last system error in s and ms since 1970-
01-01
UDINT
Fan State
Reserved: it always provides the value 0xFF for
not available
. BYTE
Main enable switch of the processor module
ON:
The subordinate enable switches can be changed.
Major CPU Release
OFF: The subordinate enable switches cannot be changed.
BOOL
Enable for non-redundant operation.
ON:
One single processor module in rack 0, slot 3 may also
start with one system bus only.
Mono Startup Release
OFF: Both system buses are also required for one single
processor module.
BOOL
ON:
The operator actions: Stop, Start, Download are locked.
Read-only in RUN
OFF: The operator actions: Stop, Start, Download are not
locked.
BOOL
Redundancy Info
Bit-coded redundancy state of the processor modules:
Bit no.
Processor Module
0 1
1 2
2 3
3 4
Bit = 0: Processor module not operating redundantly
Bit = 1: Processor module operating redundantly
All the remaining bits have the value 0.
UDINT
ON:
Controller can be loaded by performing a reload
Reload Release
OFF: Controller cannot be loaded by performing a reload
BOOL
ON:
Loading by performing a reload is locked
Reload Deactivation
OFF: Loading by performing a reload is possible
BOOL
Reload Cycle
TRUE during the first cycle after a reload, otherwise FALSE
BOOL
CPU Safety Time [ms]
Safety time set for the controller in ms
UDINT
ON:
Start of processor module using PADT is allowed
Start CPU Release
OFF: Start of processor module using PADT is not allowed
BOOL