4 Start-up
AI 8 01
Page 22 of 38
HI 800 195 E Rev. 2.00
4.3
Configuration with SILworX
In the Hardware Editor, the controller is represented with the following modules:
one processor module (CPU)
one communication module (COM)
6 slots available for I/O modules
To insert I/O modules, drag them from the module list onto an available slot.
Two variants are available for the AI 8 01 module:
AI 8 01 FS1000: Resolution of the analog value -1000…+1000 (-10…+10 V)
AI 8 01 FS2000: Resolution of the analog value -2000…+2000 (-10…+10 V)
Double-click the module to open the Detail View with the corresponding tabs. The tabs are used
to assign the global variables configured in the user program to the system parameters of the
corresponding module.
4.3.1
Parameters and Error Codes for the Inputs
The following tables specify the system parameters that can be read and set for the inputs,
including the corresponding error codes.
In the user program, the error codes can be read using the variables assigned within the logic.
The error codes can also be displayed in SILworX.