DI 32 01
4 Start-Up
HI 800 203 E Rev. 1.00
Page 23 of 38
4.3.2.1
Module
Tab
The
Module
tab contains the following system parameters.
System parameter
Data
type
R/W Description
DI Number of Pulsed
Channels
USINT
W
Number of pulsed outputs (supply outputs)
Coding
Description
0
No output planned for LS/LB
1)
detection
1
Output channnel 1 planned for LS/LB
1)
detection
2
Output channels 1...2 planned for LS/LB
1)
detection
... …
8
Output channels 1...8 planned for LS/LB
1)
detection
Pulsed outputs must not be used as safety-related outputs!
DI Pulse
Slot
UDINT W Pulse module slot: Value 1...6, according to the actual slot on
the right of the CPU
DI Pulse
Delay[10E-6 s]
UINT W Waiting time for line control (detection of short-circuits or
cross-circuits)
DI.Error Code
WORD
R
Error codes for all digital inputs
Coding
Description
0x0001 Module
fault
0x0002
FTT test of test pattern faulty
0x0004
FTT test: 1st temperature threshold
exceeded
0x0008
FTT test: 2nd Temperature threshold
exceeded
Module Error Code
WORD
R
Module error code
Coding
Description
0x0000
I/O processing, if required with errors
see other error codes
0x0001
No I/O processing (CPU not in RUN)
0x0002
No I/O processing during the booting test
0x0004
Manufacturer interface operating
0x0010
No I/O processing: wrong configuration
0x0020
No I/O processing: fault rate exceeded
0x0040/
0x0080
No I/O processing: configured module not
plugged in
Module SRS
UDINT
R
Slot number (System Rack Slot)
Module Type
UINT
R
Type of module, target value: 0xF807 [63495
dec
]
1)
LS/LB (short-circuits/open-circuits)
Table 11: SILworX - System Parameters for Digital Inputs, Module Tab