DI 32 01
4 Start-Up
HI 800 203 E Rev. 1.00
Page 25 of 38
4.4.3
Digital inputs
System Signal
R/W
Description
Mod.SRS [UDINT]
R
Slot number (System Rack Slot)
Mod. Type [UINT]
R
Type of module,target value: 0xF807 [63495
dec
]
Mod. Error Code
[WORD]
R
Error codes for the module
Coding
Description
0x0000
I/O processing, if required with errors
see other error codes
0x0001
No I/O processing (CPU not in RUN)
0x0002
No I/O processing during the booting test
0x0004
Manufacturer interface operating
0x0010
No I/O processing: wrong configuration
0x0020
No I/O processing: fault rate exceeded
0x0040/
0x0080
No I/O processing: configured module not plugged in
DI.Error Code
[WORD]
R
Error codes for all digital inputs
Coding
Description
0x0001 Module
fault
0x0002
FTT test of test pattern faulty
0x0004
FTT test: 1st temperature threshold exceeded
0x0008
FTT test: 2nd Temperature threshold exceeded
DI[xx].Error Code
[BYTE]
R
Error codes for the digital input channels
Coding
Description
0x01
Fault in the analog input module
0x10
Short-circuit of the channel
0x80
Intermittence between pulsed output DO and digital
input DI, e.g.,
Open-circuit
Open
switch
L+ low voltage
DI[xx].Value [BOOL]
R
Input values for the digital input channels
0 = input de-energized
1 = input energized
DI Number of
Pulsed Channels
[USINT]
W
Number of pulsed outputs (supply outputs)
Coding
Description
0
No output planned for LS/LB
1)
detection
1
Output channnel 1 planned for LS/LB
1)
detection
2
Output channels 1...2 planned for LS/LB
1)
detection
... …
8
Output channels 1...8 planned for LS/LB
1)
detection
Pulsed outputs must not be used as safety-related outputs!
DI Pulse.
Slot
[UDINT]
W
Pulse module slot: Value 1...6, according to the actual slot on the right of
the CPU
DI[xx].Pulsed
Channel [USINT]
W
Source channel for pulsed supply
Coding
Description
0 Input
channel
1
Pulse of the 1st DO channel
2
Pulse of the 2nd DO channel
... ...
8
Pulse of the 8th DO channel