3 Product Description
DI 32 01
Page 12 of 38
HI 800 203 E Rev. 1.00
EMERGENCY STOP 1
EMERGENCY STOP 2
EMERGENCY STOP devices in
accordance with EN 60947-5-1 and
EN 60947-5-5
Figure 1:
Line Control
The device pulses the pulsed outputs to monitor the wires to the digital inputs. To do so,
configure the
Value [BOOL] ->
system variable in SILworX or the
DO[01].Value
system
signal in ELOP II Factory
.
The variables for the pulsed outputs must begin with channel 1
and reside in direct sequence, one after the other.
If the following faults occur, the
FAULT
LED located on the front plate of the controller
blinks, the inputs are set to low level and an (evaluable) error code is created:
Cross-circuit between two parallel lines,
Improper connections of two lines (e.g., TO 2 to DI 3),
Earth fault of a line (with earthed ground only),
Open-circuit or open contacts, i.e., including when one of the two EMERGENCY STOP
switches mentioned above has been engaged, the
FAULT
LED blinks and the error
code is created.
For more information on how to configure line control in the user program, refer to the
HIMatrix Engineering Manual.