The interface on connector X3 of the PKV 30-IBS is designed for
communication
respectively for
diagnostic/configuration
If the power of the protocol converter is switched on, it checks the serial interface
if the diagnostic/configuration mode should be activated, otherwise it starts the
communication mode.
2.4.1 Activation of the diagnostic/configuration mode
Connect the diagnostic cable on X3 of the protocol converter and to COM1 (or
COM2) of the PC.
Start the program ComPro
COMPRO /S:1
respectively.
COMPRO /S:2
(for COM1 respectively COM2).
Select menu
online - system - bootstart.
A windows appears that shows
The sy-
stem will be reseted and the bootloader becomes active without starting any
firmware
.
Turn off power of the protocol converter and wait at least 10 seconds.
Accept the message
The system will be reseted and the bootloader becomes acti-
ve without starting any firmware
with press the Enter key. A red window appears
that shows
Waiting for hardware receipt
.
Power on the protocol converter.
The red window disappears.
To test if the protocol converter is in diagnostic/configuration mode select menu
online system - firmware.
If a window appears and shows the name of the firm-
ware, then the diagnostic/configuration mode is active. If the message
Connection
could not be established or connection lost
appears, then try to activate the dia-
gnostic/configuration mode again according to the steps described above.
General device description
12