UNIT MAINTENANCE
7.4.1
Electrical system and control devices
Operations to be performed
Frequency
Every
month
Every
6 months
Every
year
When
required
Check that the unit is working properly and that there are no alarms
Inspect the unit visually
Check the noise and vibration of the unit
Check the functionality of the safety devices and interlocks
Check the performance of the unit
Check the electrical consumption of the various utilities (compressors, fans, etc.)
Check the supply voltage of the unit
Check the fixing of the cables in the relative terminals
Check the integrity of the insulating coating of the electric cables
Check the status and operation of the contactors
Check the functioning of the microprocessor and of the display
Clean the electrical and electronic components from any dust present
Check the operation and calibration of the probes and transducers
7.4.2
Refrigerant and hydraulic circuits
Operations to be performed
Frequency
Every
month
Every
6 months
Every
year
When
required
Check the pressure of the hydraulic circuits and any leaks
Check that the flow switch is working properly
Clean the metal filter placed on the water pipe (1)
Check the 4-way valve operation (if present)
Check for the presence of air in the hydraulic circuit
Check the colour of the humidity indicator
Check for freon leaks (2)
(1)
It can be performed more frequently (even weekly) depending on the temperature difference.
(2)
To perform operations on the refrigerant it is necessary to comply with the European regulation 517_2014, “Obligations
arising in relation to the containment, use, recovery and destruction of fluorinated greenhouse gases used in fixed
refrigeration, air conditioning and heat pump equipment ".
Rev. C 09-2020
MTEC.3810.GB-C-1 Operation and maintenance manual serie WZA English
45