4
GEO
HFE 06
HFE 08
HFE 12
HFE 16
HFE 20
HFE 24
V/~/Hz
230/1/50
230/1/50
230/1/50
400/3+N/50
400/3+N/50
400/3+N/50
V
24
24
24
24
24
24
V
230
230
230
230
230
230
mm²
6 / 2,5
10 / 2,5
16 / 2,5
4
6
6
mm²
4 / 1,5
6 / 1,5
10 / 1,5
2,5
4
4
GEO
HFE 33
HFE 42
HFS 60
HFS 80
HFS 100
V/~/Hz
400/3/50+N
400/3/50+N
400/3/50+N
400/3/50+N
400/3/50+N
V
24
24
24
24
24
V
230
230
230
230
230
mm²
10
16
25
25
35
mm²
6
10
16
16
25
HFS 60÷100
HFE 06÷42
INSTALLATION
4.16 ELECTRICAL
DATA
The following electrical data refer to the standard unit without accessories.
In all other cases, refer to the electrical data shown in the annexed wiring diagrams.
The supply voltage must not undergo variations of more than ±10% of the nominal value and the imbalance between the
phases must be less than 1% according to the EN 60204 standard. If these tolerances are not observed, please contact our
technical department.
The electrical data may change without notice. It is therefore necessary to always refer to the wiring diagram supplied with
the unit.
Electrical power supply
Control circuit
Auxiliary circuit
Line section
(single-phase/three-phase)
PE section
(single-phase/three-phase)
Electrical power supply
Control circuit
Auxiliary circuit
Line section
(single-phase/three-phase)
PE section
(single-phase/three-phase)
4.17 ELECTRICAL
CONNECTIONS
4.17.1
Power supply connection
Electrical connections
input
Electrical power supply
input
Electrical connections input
Electrical power supply input
Rev. C 09-2020
MTEC.3810.GB-C-1 Operation and maintenance manual serie WZA English
31
WZA
06
08
12
16
20
24
33
40
WZA