HIDRIA 0318-4-1005 Скачать руководство пользователя страница 7

USER'S GUIDE R18 AXIAL FAN , Iss: 6.05.2021

05

SPEED CONTROL DIAGRAM

Rotation speed of a variable speed fan can be controlled by various signals:

- Linear voltage input (0-10V) or current input (4-20mA) or PWM input (PWM duty cycle 0-100%).
- MODBUS RTU protocol (Additional information are in documentation "Hidria EC Modbus parameters".

Linear voltage input is the most common and it is described below. The current input is also widely used, where long cables are necessary. PWM input
is used for electromagnetic noisy environments. PWM signal must be in square form with polarity the same as for linear voltage input (see connection
diagram). PWM duty cycle 0-100% correspond to 0-10V linear voltage input if the amplitude of the PWM voltage is Vp=10V. Amplitude of PWM signal
must not exceed 12Vp.

LINEAR VOLTAGE INPUT:

Linear input is factory adjusted to fit the customer’s sensor or other speed control reference. The input characteristic can be factory adjusted in terms of
increasing input sensitivity or attenuation. 

For example: An air-cooled condenser is using a pressure sensor 0-20Bar => 0-10V, but the highest system pressure reached at maximum load is
16Bar => 8V. For optimal operation of the application the fan mounted on a condenser should run at max speed at 8V of input control voltage. In order
to achieve that, we need to adjust the input characteristic in a way the picture shows. 

1.0V

1,2V

Input voltage (0

10V)

Fa

n

 s

p

e

e

d

HYSTERESIS

100%

1.2V

10V

Input voltage (0

10V)

Fan speed

CONTROL DIAGRAM

8V

adjusted

input curve

100%

1.2V

10V

Input voltage (0

10V)

Fan speed

INPUT CHARACTERISTIC ADJUSTMENT

0

200

400

600

800

1000

1200

Fa

n

 r

o

ta

ti

o

n

a

sp

e

e

d

 (R

P

M

)

Input Voltage (0...10 V)

SPEED CONTROL DIAGRAM

1.2 V

10 V

5 V

O

N

/O

F

F

 

H

Y

S

T

E

R

E

S

IS

D

=

0

.2

V

In order to prevent cycling from standby to run mode or run to standby 
mode a small hysteresis is implemented. The default value is 
approximately 200mV. 
Hysteresis can be factory-adjusted in order to achieve customer 
requirements.

Linear voltage input (0-10V DC) can be used as 0 (4)-20mA current 
input with an additional resistor of 500 Ohms between GND and 0-10V 
connection.

Speed of a fan increases linearly with input voltage. 

The fan operates in two different modes:
0-1.2 V…… Standby or stop mode
1.2-10 V….. Run mode
1.0-1.2V .....Hysteresis

© Copyright  HIDRIA d.o.o., All rights reserved. Document is subject to change without prior notification.

7 / 10

Содержание 0318-4-1005

Страница 1: ... ROHS AND EMC DIRECTIVES 12 SERVICE ADDRESSES AND ADDITIONAL DATA This document contains instructions and information for the operation installation connection use and maintenance of the product Be sure to familiarize yourself with these instructions before working on this unit Not paying attention to these warnings and instructions may lead to malfunctions and failures or may seriously endanger h...

Страница 2: ...arm Do not operate this appliance in an explosive atmosphere Fan must be fixed to stationary housing with appropriate screws according to this guide This appliance is not intended to be built as a partition fan The electrical connection must correspond to this installation guide and enclosed connecting diagram as desribed in chapter 4 INSTALLATION AND CONNECTION page 6 of this document Means for d...

Страница 3: ...s not intended to be built as a partition fan mounting in outside windows or walls unless it is built into an end application which is designed for that purpose The fan is intended to be permanently connected to fixed wiring The fan is intended to be connected to electrical power supply system with earthed neutral e g of type TN TT The fans are only to be operated within the ranges specified on th...

Страница 4: ...densing Max pressure 260 Pa ErP DATA Overall Efficiency Effes 47 8 Installation category A Efficiency category static Efficiency grade N 51 4 Variable speed drive INTEGRATED Power Input Pelec 2708 1 W Airflow volume qV 18519 m h Pressure Increase ps 250 Pa Rotational Speed n 1146 RPM Specific ratio 1 002 Airflow volume max qV 27336 m h Pressure Increase max ps 610 Pa 1 Fan type and code 2 Trade ma...

Страница 5: ... possible injuries the height and the diameter of inlet cone must be appropriate dimensions To lift the device with lifting devices use the hangers provided for this purpose as shown on figure below Always use suitable lifting equipment and follow the instructions for safe work with lifting equipment Failure to follow the instructions for safe work can lead to equipment damage or may seriously end...

Страница 6: ...ing plug must remain in the gland Connection box screws have to be tightened with torque of 2 0Nm 2 5Nm Secure connection cable to the fan guard grill or to the motor holder with cable fasteners so that the water flows away from the cable and cable gland Try to maintain as much distance between supply and control cable as possible recommended distance 5cm Cable end of the fan must be connected in ...

Страница 7: ...V but the highest system pressure reached at maximum load is 16Bar 8V For optimal operation of the application the fan mounted on a condenser should run at max speed at 8V of input control voltage In order to achieve that we need to adjust the input characteristic in a way the picture shows 1 0V 1 2V Input voltage 0 10V Fan speed HYSTERESIS 100 1 2V 10V Input voltage 0 10V Fan speed CONTROL DIAGRA...

Страница 8: ... correct value the motor will restart automatically In the specific case the undervoltage protection may switch off the fan to stand by mode for example fan running or testing at high pressure drop and low voltage Over temperature protection Internally connected thermal protector to protect electronic and motor against over temperature 06 PUTTING INTO OPERATION Before first start you should check ...

Страница 9: ...n in circuit of electronics windings never try to repair the fan but replace it with new one or and return defected fan to the manufacturer for repair or replacement ALARM RELAY DIAGNOSTICS Alarm relay contact OPEN on ERROR Alarm relay contacts capability max 2A 250VAC cos fi0 6 max 3A 30VDC Errors on which alarm relay OPEN Rotor locked in duration exceeding 10s Motor winding overheating Power mod...

Страница 10: ...o protection grill Do not apply any force for the cable s When transporting fans mounted on final units apparatus take care that they are properly secured and don t touch other devices which are transported near or on to Store the fans in the original packaging in a dry area protected from the weather Do not store fans in extreme heat and cold We recommend a maximum of one year of storage After a ...

Отзывы: