USER'S GUIDE R18 AXIAL FAN , Iss: 6.05.2021

04

INSTALLATION AND CONNECTION

Mechanical installation:

This unit should only be installed by a qualified technician. Inspect the motor bearings for proper operation prior to installation.

Do not install the fan on an unstable surface. First install the device on the application, than connect the protective earth!

The method of fixing stated is not to depend on the use of adhesives since they are not considered to be a reliable fixing means.

The fan is primarily constructed for installation with rotor on bottom or with shaft in horizontal. For other possibilities please contact for manufacturer's
support.

Ensure that the air-gap between the fan impeller and the stationary housing is constant. Distortion due to an uneven surface of basis may lead to a fan
failure. Air-gap between blade and cone-inlet (housing) should be of min. 3 mm. 

Fan must be fixed to stationary housing 8x M8 through 8 holes on diameter 816 mm of protection grid as indicated on enclosed technical drawing. Use
screws with property class of 8.8. Secure all threaded joints with e.g. Loctite or by using self-locking screws. 

The system manufacturer or the machine builder is responsible that the inherent installation and security information are harmonized with the valid
standards and guidelines (ex. EN 13857). To prevent dangerous situation and possible injuries the height and the diameter of inlet cone must be
appropriate dimensions. 

To lift the device with lifting devices, use the hangers provided for this purpose as shown on figure below. Always use suitable lifting equipment and
follow the instructions for safe work with lifting equipment. Failure to follow the instructions for safe work can lead to equipment damage or may
seriously endanger human life.

Electrical installation:

Main electrical installation must be protected against short circuit with e.g. circuit breaker: max.16A, 400Vac, Type B and installation must be
constructed properly according to valid national directives. 

First install the device on the application, than connect the protective earth!

Means for disconnection must be incorporated in the fixed wiring in accordance with the wiring rules.

The fan is intended only to be connected to the fixed wiring or application’s circuit. An all-pole separating switch which must be incorporated to wiring
must disconnect also the fan.

This product can cause a d.c. current in the protective earthing conductor. Where a residual current-operated protective device (RCD) or monitoring
(RCM) device is used for protection in case of direct or indirect contact, only an RCD or RCM of Type B+ is allowed on the supply side of this product
and recommended sensitivity is 300mA with short time delayed intervention.

The electrical connection must correspond to the enclosed connection diagram.

© Copyright  HIDRIA d.o.o., All rights reserved. Document is subject to change without prior notification.

5 / 10

Содержание 0318-4-1005

Страница 1: ... ROHS AND EMC DIRECTIVES 12 SERVICE ADDRESSES AND ADDITIONAL DATA This document contains instructions and information for the operation installation connection use and maintenance of the product Be sure to familiarize yourself with these instructions before working on this unit Not paying attention to these warnings and instructions may lead to malfunctions and failures or may seriously endanger h...

Страница 2: ...arm Do not operate this appliance in an explosive atmosphere Fan must be fixed to stationary housing with appropriate screws according to this guide This appliance is not intended to be built as a partition fan The electrical connection must correspond to this installation guide and enclosed connecting diagram as desribed in chapter 4 INSTALLATION AND CONNECTION page 6 of this document Means for d...

Страница 3: ...s not intended to be built as a partition fan mounting in outside windows or walls unless it is built into an end application which is designed for that purpose The fan is intended to be permanently connected to fixed wiring The fan is intended to be connected to electrical power supply system with earthed neutral e g of type TN TT The fans are only to be operated within the ranges specified on th...

Страница 4: ...densing Max pressure 260 Pa ErP DATA Overall Efficiency Effes 47 8 Installation category A Efficiency category static Efficiency grade N 51 4 Variable speed drive INTEGRATED Power Input Pelec 2708 1 W Airflow volume qV 18519 m h Pressure Increase ps 250 Pa Rotational Speed n 1146 RPM Specific ratio 1 002 Airflow volume max qV 27336 m h Pressure Increase max ps 610 Pa 1 Fan type and code 2 Trade ma...

Страница 5: ... possible injuries the height and the diameter of inlet cone must be appropriate dimensions To lift the device with lifting devices use the hangers provided for this purpose as shown on figure below Always use suitable lifting equipment and follow the instructions for safe work with lifting equipment Failure to follow the instructions for safe work can lead to equipment damage or may seriously end...

Страница 6: ...ing plug must remain in the gland Connection box screws have to be tightened with torque of 2 0Nm 2 5Nm Secure connection cable to the fan guard grill or to the motor holder with cable fasteners so that the water flows away from the cable and cable gland Try to maintain as much distance between supply and control cable as possible recommended distance 5cm Cable end of the fan must be connected in ...

Страница 7: ...V but the highest system pressure reached at maximum load is 16Bar 8V For optimal operation of the application the fan mounted on a condenser should run at max speed at 8V of input control voltage In order to achieve that we need to adjust the input characteristic in a way the picture shows 1 0V 1 2V Input voltage 0 10V Fan speed HYSTERESIS 100 1 2V 10V Input voltage 0 10V Fan speed CONTROL DIAGRA...

Страница 8: ... correct value the motor will restart automatically In the specific case the undervoltage protection may switch off the fan to stand by mode for example fan running or testing at high pressure drop and low voltage Over temperature protection Internally connected thermal protector to protect electronic and motor against over temperature 06 PUTTING INTO OPERATION Before first start you should check ...

Страница 9: ...n in circuit of electronics windings never try to repair the fan but replace it with new one or and return defected fan to the manufacturer for repair or replacement ALARM RELAY DIAGNOSTICS Alarm relay contact OPEN on ERROR Alarm relay contacts capability max 2A 250VAC cos fi0 6 max 3A 30VDC Errors on which alarm relay OPEN Rotor locked in duration exceeding 10s Motor winding overheating Power mod...

Страница 10: ...o protection grill Do not apply any force for the cable s When transporting fans mounted on final units apparatus take care that they are properly secured and don t touch other devices which are transported near or on to Store the fans in the original packaging in a dry area protected from the weather Do not store fans in extreme heat and cold We recommend a maximum of one year of storage After a ...