USER'S GUIDE R18 AXIAL FAN , Iss: 6.05.2021

03

OPERATING CONDITIONS

The fans are rated for S1 (IEC 60034-1) continuous operation.

Extreme ON-OFF switching operating must be avoided, because it has negative influence on life expectancy and power consumption.

Cycling operating mode should only with cycling ON/OFF via control signal (0/10V analog input or PWM input).

Do not cycling the power supply for cycling operating mode – use control signal! High 'In-rush current' can occur during cycling power supply!

Permissible ambient temperature is specified as indicated on the motor nameplate for actual fan and in chapter 03 OPERATING CONDITIONS in the
INSTALLATION, MAINTENANCE AND USER'S GUIDE.

If the end use requires compliance with the IEC/EN 60335 standards, due to the temperature limitation of the connecting cable, the temperature range
of the fan is limited to max. + 60 °C, even if the fan on the nameplate is specified for use up to a higher ambient temperature. If the fan is used at an
ambient temperature above 60 °C, always use temperature-resistant cables (PVC 105°C).

Figures on the motor name-plate refer to nominal values according to rule specified on the nameplate next to the written values. The rules (EN_60335,
'free air', 'max.load', 'max.eff.',  cust. unit / cust. spec., UL, IEC 60034-1) are described in the example shown below.

Continuous sound pressure level may exceed 70dBA (depends of fan model).

Protection (motor & electronics): IP55 according to EN60529.

Power consumption in stand-by mode: les than 5W.

DIMENSIONS 

Nominal diameter: 800 mm - see Appendix - technical drawing: VENTILATOR / R18R-080MPS-ET120B-01A01

Weight: 50 kg 

 NOMINAL DATA - defined according to ' MAX. LOAD '

Phase: 3~

Nominal Voltage: 400 V

Operating Voltage range: 380-480 V

Frequency: 50 Hz

Input power: 2900 W

Nominal current: 4,6 A

Rotational speed: 1140 RPM

Operating ambient temperature range: -25°C .. +65°C

Altitude: 2000 m

Insulation class: 155

Protection provided by PE: Class I 

Overvoltage category (OVC): III 

Operating humidity ambient: up to 95% (non condensing).

Max. pressure: 260 Pa

ErP DATA

Overall Efficiency, Effes: 47,8 %

Installation category: A

Efficiency category: static

Efficiency grade, N: 51,4

Variable speed drive: INTEGRATED

Power Input , Pelec: 2708,1 W

Airflow volume , qV: 18519 m³/h

Pressure Increase, ps: 250 Pa

Rotational Speed, n: 1146 RPM

Specific ratio: 1,002

Airflow volume max., qV: 27336 m³/h

Pressure Increase max., ps: 610 Pa

1. Fan type and code
2. Trade mark and manufacturer address
3. Nominal values (Voltage, frequency, Electric Power, Current...)
4. Certification marks
5. Date of production (week of the year/year)
6. QR code which includes code number, production date, serial number 
and link to website.
7. Data acc. to EU regulation 327/2011 (ErP)
8. NOTE INDICATE TO WHICH STANDARD/RULES CORESPOND DATA ON THE 
NAMEPLATE:

- EN 60335-1 

: Name-plate data are made according to standard EN 

60335-1, Household and similar electrical appliances – Safety – Part 1, 
Articles 10.1 and 10.2:
If an appliance is marked with rated power input, the power input at 
normal operating temperature shall not deviate from the rated power 
input by more than: + 20% if Pn<300W or  +15% (or 60W whichever is 
the greater)  if Pn>300W.
If an appliance is marked with rated current, the current at normal 
operating temperature shall not deviate from the rated current by more 
than: +20% if In<1.5A or  +15% (or 0,30A whichever is the greater)  if 
In>1.5A.

- FREE AIR

: Data on the nameplate established at a point 0Pa static 

pressure at normal operating temperature.

- MAX LOAD 

: Data on the nameplate established at a point of maximal 

static pressure regarding max. ambient 

temperature

.

- MAX. EFF. 

: Data on the nameplate established at a point of maximal 

static efficiency at normal operating temperature.

- CUST. UNIT / CUST. SPEC.

: Data on the nameplate specified according 

to customer specifications or at working point in customer's unit .

- UL

- Data on the nameplate defined according to specifications in UL 

standards.

- IEC 60034-1 

- Data on the nameplate established at a point of nominal 

load according to standard for Rotational electrical machines.

An example of a label and explanation of the content

:

1

2

5

6

7

8

3

4

© Copyright  HIDRIA d.o.o., All rights reserved. Document is subject to change without prior notification.

4 / 10

Содержание 0318-4-1005

Страница 1: ... ROHS AND EMC DIRECTIVES 12 SERVICE ADDRESSES AND ADDITIONAL DATA This document contains instructions and information for the operation installation connection use and maintenance of the product Be sure to familiarize yourself with these instructions before working on this unit Not paying attention to these warnings and instructions may lead to malfunctions and failures or may seriously endanger h...

Страница 2: ...arm Do not operate this appliance in an explosive atmosphere Fan must be fixed to stationary housing with appropriate screws according to this guide This appliance is not intended to be built as a partition fan The electrical connection must correspond to this installation guide and enclosed connecting diagram as desribed in chapter 4 INSTALLATION AND CONNECTION page 6 of this document Means for d...

Страница 3: ...s not intended to be built as a partition fan mounting in outside windows or walls unless it is built into an end application which is designed for that purpose The fan is intended to be permanently connected to fixed wiring The fan is intended to be connected to electrical power supply system with earthed neutral e g of type TN TT The fans are only to be operated within the ranges specified on th...

Страница 4: ...densing Max pressure 260 Pa ErP DATA Overall Efficiency Effes 47 8 Installation category A Efficiency category static Efficiency grade N 51 4 Variable speed drive INTEGRATED Power Input Pelec 2708 1 W Airflow volume qV 18519 m h Pressure Increase ps 250 Pa Rotational Speed n 1146 RPM Specific ratio 1 002 Airflow volume max qV 27336 m h Pressure Increase max ps 610 Pa 1 Fan type and code 2 Trade ma...

Страница 5: ... possible injuries the height and the diameter of inlet cone must be appropriate dimensions To lift the device with lifting devices use the hangers provided for this purpose as shown on figure below Always use suitable lifting equipment and follow the instructions for safe work with lifting equipment Failure to follow the instructions for safe work can lead to equipment damage or may seriously end...

Страница 6: ...ing plug must remain in the gland Connection box screws have to be tightened with torque of 2 0Nm 2 5Nm Secure connection cable to the fan guard grill or to the motor holder with cable fasteners so that the water flows away from the cable and cable gland Try to maintain as much distance between supply and control cable as possible recommended distance 5cm Cable end of the fan must be connected in ...

Страница 7: ...V but the highest system pressure reached at maximum load is 16Bar 8V For optimal operation of the application the fan mounted on a condenser should run at max speed at 8V of input control voltage In order to achieve that we need to adjust the input characteristic in a way the picture shows 1 0V 1 2V Input voltage 0 10V Fan speed HYSTERESIS 100 1 2V 10V Input voltage 0 10V Fan speed CONTROL DIAGRA...

Страница 8: ... correct value the motor will restart automatically In the specific case the undervoltage protection may switch off the fan to stand by mode for example fan running or testing at high pressure drop and low voltage Over temperature protection Internally connected thermal protector to protect electronic and motor against over temperature 06 PUTTING INTO OPERATION Before first start you should check ...

Страница 9: ...n in circuit of electronics windings never try to repair the fan but replace it with new one or and return defected fan to the manufacturer for repair or replacement ALARM RELAY DIAGNOSTICS Alarm relay contact OPEN on ERROR Alarm relay contacts capability max 2A 250VAC cos fi0 6 max 3A 30VDC Errors on which alarm relay OPEN Rotor locked in duration exceeding 10s Motor winding overheating Power mod...

Страница 10: ...o protection grill Do not apply any force for the cable s When transporting fans mounted on final units apparatus take care that they are properly secured and don t touch other devices which are transported near or on to Store the fans in the original packaging in a dry area protected from the weather Do not store fans in extreme heat and cold We recommend a maximum of one year of storage After a ...

Отзывы: