USER'S GUIDE R14 AXIAL FAN , Code: 0000, Iss: 9.07.2019

05

SPEED CONTROL

Rotation speed of a variable speed fan can be controlled by various signals:

- Linear voltage input (0-10V) or current input (4-20mA) or PWM input (PWM duty cycle 0-100%).
- MODBUS RTU protocol (Additional information are in documentation "Hidria EC Modbus parameters" and on www.modbus.org.
- Slave control output.

Linear voltage input is the most common and it is described below. The current input is also widely used, where long cables are necessary. PWM input
is used for electromagnetic noisy environments. PWM signal must be in square form with polarity the same as for linear voltage input (see connection
diagram). PWM duty cycle 0-100% correspond to 0-10V linear voltage input if the amplitude of the PWM voltage is Vp=10V. Amplitude of PWM signal
must not exceed 12Vp.

LINEAR VOLTAGE INPUT:

Linear input is factory adjusted to fit the customer’s sensor or other speed control reference. The input characteristic can be factory adjusted in terms of
increasing input sensitivity or attenuation. 

For example: An air-cooled condenser is using a pressure sensor 0-20Bar => 0-10V, but the highest system pressure reached at maximum load is
16Bar => 8V. For optimal operation of the application the fan mounted on a condenser should run at max speed at 8V of input control voltage. In order
to achieve that, we need to adjust the input characteristic in a way the picture shows. 

1.0V

1,2V

Input voltage (0

10V)

Fa

n

 s

p

e

e

d

HYSTERESIS

100%

1.2V

10V

Input voltage (0

10V)

Fan speed

CONTROL DIAGRAM

8V

adjusted

input curve

100%

1.2V

10V

Input voltage (0

10V)

Fan speed

INPUT CHARACTERISTIC ADJUSTMENT

0

200

400

600

800

1000

1200

1400

Fa

n

 r

o

ta

ti

o

n

a

sp

e

e

d

 (R

P

M

)

Input Voltage (0...10 V)

SPEED CONTROL DIAGRAM

1.2 V

10 V

5 V

In order to prevent cycling from standby to run mode or run to standby 
mode a small hysteresis is implemented. The default value is 
approximately 200mV. 
Hysteresis can be factory-adjusted in order to achieve customer 
requirements.

Speed of a fan increases linearly with input voltage. 

The fan operates in two different modes:
0-1.2 V…… Standby or stop mode
1.2-10 V….. Run mode
1.0-1.2V .....Hysteresis

Linear voltage input (0-10V DC) can be used as 0 (4)-20mA current 
input with an additional resistor of 500 Ohms between GND and 0-10V 
connection.

© Copyright  HIDRIA d.o.o., All rights reserved. Document is subject to change without prior notification.

7 / 9

Содержание 0314-4-0089

Страница 1: ...G INTO OPERATION 07 DIAGNOSTICS TROUBLESHOOTING 08 PROTECTIVE FEATURES 09 MAINTENANCE SERVICE AND CLEANING 10 TRANSPORT AND STORAGE 11 ErP ROHS AND EMC DIRECTIVES 12 SERVICE ADDRESSES AND ADDITIONAL D...

Страница 2: ...dental contact according to machinery directive 2006 42 CE has to be safeguarded especially for the rotating parts Should there be a malfunction it still has to be safeguarded that the parts breaking...

Страница 3: ...nce is not intended to be built as a partition fan mounting in outside windows or walls unless it is built into an end application which is designed for that purpose The fan is intended to be permanen...

Страница 4: ...fes 50 2 Installation category A Efficiency category static Efficiency grade N 57 8 Variable speed drive INTEGRATED Power Input Pelec 630 1 W Airflow volume qV 6608 m h Pressure Increase ps 160 Pa Rot...

Страница 5: ...onnection must correspond to the enclosed connection diagram Recommended cable for power supply and alarm relay contact is an ordinary PVC cable acc to IEC 60227 5 eg H05V2V2 F 4G 1 mm no longer than...

Страница 6: ...A RS B 0 10V analog input 0 10V GND 4 20mA analog input 4 20mA GND Sensor supply 10V GND or 20V GND Slave control OUT GND The device is compatible with Modbus protocol RTU Please read additional inst...

Страница 7: ...g a pressure sensor 0 20Bar 0 10V but the highest system pressure reached at maximum load is 16Bar 8V For optimal operation of the application the fan mounted on a condenser should run at max speed at...

Страница 8: ...pply voltage inadequate control signal or fan overheating Check line voltage check control signal check temperature and sufficient airflow of cooling air or loss of motor cooling Attention In the even...

Страница 9: ...orce for the cable s When transporting fans mounted on final units apparatus take care that they are properly secured and don t touch other devices which are transported near or on to Store the fans i...

Отзывы: